Inspections for the day of: Thursday, December 13, 2007.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00327 INSP-Alarm Testing12/13/200712/13/200712/13/2007 5:08:26 PMPPASS
Fire alarm testing passed, c/n complete.
FIR07-00328 INSP-Alarm Testing12/13/200712/13/200712/13/2007 5:07:38 PMPPASS
Corrections are complete, inspection passed.
FIR07-00663 INSP-Sprinkler Rough-in/Hydro12/13/200712/13/200712/13/2007 5:02:10 PMPPART
Missing one head at the pantry, remainder of the OH rough-in is acceptable, riser is not yet built, need to provide cold cavity protection as detailed.
FIR07-00329 INSP-Final Inspection12/13/200712/13/200712/13/2007 4:58:52 PMPPASS
FA permit finaled.
FIR07-00330 INSP-Final Inspection12/13/200712/13/200712/13/2007 4:58:19 PMPPASS
Final inspection passed, permit finaled.
FIR07-00331 INSP-Final Inspection12/13/200712/13/200712/13/2007 4:56:53 PMPPASS
Inspection passed, permit finaled.
FIR07-00319 INSP-Final Inspection12/13/200712/13/200712/13/2007 4:56:20 PMPPASS
FA permit finaled.
FIR07-00322 INSP-Final Inspection12/13/200712/13/200712/13/2007 4:53:47 PMPPASS
FA permit passed final inspection.
FIR07-00825 INSP-Final Inspection12/13/200712/13/200712/13/2007 4:53:03 PMPPASS
Permit finaled.
FIR07-00937 INSP-Sprinkler Rough-in12/13/200712/13/200712/13/2007 2:06:48 PMPCANC
Inspection to be rescheduled as discussed, noted contractor has been issued the permit and called for a system rough-in inspection the same day.
FIR07-00882 INSP-Final Inspection12/13/200712/13/200712/13/2007 2:03:56 PMPFAIL
Noted locations on the plan in need of revision including one blocked head, one head to be replaced, one pendent is too low, spacing at one area if a closet is not built as indicated on plans.
BLD07-02862 FIRE-Final Inspection12/12/200712/13/200712/13/2007 12:32:07 PMAPASS
Life safety inspection passed, noted door closure at the main entry to be installed prior to sturctural final.
FIR07-00879 INSP-Sprinkler Rough-in12/12/200712/13/200712/13/2007 12:31:02 PMAPART
Okay to cover the UG fire supply line to the point as initialed and annotated on approved plan set.
FIR07-00825 INSP-Final Inspection12/12/200712/13/200712/13/2007 12:29:12 PMAPASS
Fire sprinkler passed final inspection, permit finaled.
BLD07-00960 FIRE-Final Inspection12/12/200712/13/200712/13/2007 12:28:31 PMAPASS
Fire life safety inspection completed satisfactory.
FIR07-00976 INSP-Sprinkler Rough-in/Hydro12/12/200712/13/200712/13/2007 12:27:16 PMAFAIL
UG hydrostatic test failed due to a 5 psi. loss at the guage.
FIR07-00649 FIR-Aging Inspection12/13/200712/13/200712/13/2007 8:11:49 AM DEFR
Work in progress.