FIR07-00327
| INSP-Alarm Testing | 12/13/2007 | 12/13/2007 | 12/13/2007 5:08:26 PM | P | PASS |
|
|
Fire alarm testing passed, c/n complete.
|
FIR07-00328
| INSP-Alarm Testing | 12/13/2007 | 12/13/2007 | 12/13/2007 5:07:38 PM | P | PASS |
|
|
Corrections are complete, inspection passed.
|
FIR07-00663
| INSP-Sprinkler Rough-in/Hydro | 12/13/2007 | 12/13/2007 | 12/13/2007 5:02:10 PM | P | PART |
|
|
Missing one head at the pantry, remainder of the OH rough-in is acceptable, riser is not yet built, need to provide cold cavity protection as detailed.
|
FIR07-00329
| INSP-Final Inspection | 12/13/2007 | 12/13/2007 | 12/13/2007 4:58:52 PM | P | PASS |
|
|
FA permit finaled.
|
FIR07-00330
| INSP-Final Inspection | 12/13/2007 | 12/13/2007 | 12/13/2007 4:58:19 PM | P | PASS |
|
|
Final inspection passed, permit finaled.
|
FIR07-00331
| INSP-Final Inspection | 12/13/2007 | 12/13/2007 | 12/13/2007 4:56:53 PM | P | PASS |
|
|
Inspection passed, permit finaled.
|
FIR07-00319
| INSP-Final Inspection | 12/13/2007 | 12/13/2007 | 12/13/2007 4:56:20 PM | P | PASS |
|
|
FA permit finaled.
|
FIR07-00322
| INSP-Final Inspection | 12/13/2007 | 12/13/2007 | 12/13/2007 4:53:47 PM | P | PASS |
|
|
FA permit passed final inspection.
|
FIR07-00825
| INSP-Final Inspection | 12/13/2007 | 12/13/2007 | 12/13/2007 4:53:03 PM | P | PASS |
|
|
Permit finaled.
|
FIR07-00937
| INSP-Sprinkler Rough-in | 12/13/2007 | 12/13/2007 | 12/13/2007 2:06:48 PM | P | CANC |
|
|
Inspection to be rescheduled as discussed, noted contractor has been issued the permit and called for a system rough-in inspection the same day.
|
FIR07-00882
| INSP-Final Inspection | 12/13/2007 | 12/13/2007 | 12/13/2007 2:03:56 PM | P | FAIL |
|
|
Noted locations on the plan in need of revision including one blocked head, one head to be replaced, one pendent is too low, spacing at one area if a closet is not built as indicated on plans.
|
BLD07-02862
| FIRE-Final Inspection | 12/12/2007 | 12/13/2007 | 12/13/2007 12:32:07 PM | A | PASS |
|
|
Life safety inspection passed, noted door closure at the main entry to be installed prior to sturctural final.
|
FIR07-00879
| INSP-Sprinkler Rough-in | 12/12/2007 | 12/13/2007 | 12/13/2007 12:31:02 PM | A | PART |
|
|
Okay to cover the UG fire supply line to the point as initialed and annotated on approved plan set.
|
FIR07-00825
| INSP-Final Inspection | 12/12/2007 | 12/13/2007 | 12/13/2007 12:29:12 PM | A | PASS |
|
|
Fire sprinkler passed final inspection, permit finaled.
|
BLD07-00960
| FIRE-Final Inspection | 12/12/2007 | 12/13/2007 | 12/13/2007 12:28:31 PM | A | PASS |
|
|
Fire life safety inspection completed satisfactory.
|
FIR07-00976
| INSP-Sprinkler Rough-in/Hydro | 12/12/2007 | 12/13/2007 | 12/13/2007 12:27:16 PM | A | FAIL |
|
|
UG hydrostatic test failed due to a 5 psi. loss at the guage.
|
FIR07-00649
| FIR-Aging Inspection | 12/13/2007 | 12/13/2007 | 12/13/2007 8:11:49 AM | | DEFR |
|
|
Work in progress.
|