FIR07-00816
| INSP-Sprinkler Rough-in/Hydro | 12/12/2007 | 12/13/2007 | 12/13/2007 4:27:38 PM | P | FAIL |
|
|
Hydro test passed. Backflow needs to be certified,loading dock on north side of building with awning needs to be covered w/sprinkler,sprinkler head in wharehouse office needs tape removed.KR
|
FIR07-00770
| INSP-Final Inspection | 12/12/2007 | 12/13/2007 | 12/13/2007 3:49:55 PM | A | FAIL |
|
|
I arrived at the scheduled 8:00am and found tim but no heating guy. I left and returned at 11:45am. After testing four of the five duct smoke detectors in the open sales area, one duct detector was found inoperative. The test was stopped due to time constraints.
|
FIR07-00761
| INSP-Final Inspection | 12/13/2007 | 12/13/2007 | 12/13/2007 3:34:09 PM | P | PASS |
|
|
Sprinkler permit for this scope of work finaled.KR
|
FIR07-00736
| INSP-Final Inspection | 12/12/2007 | 12/13/2007 | 12/13/2007 3:11:09 PM | A | PASS |
|
|
Test areas that we could not test during last inspection for this permit #..KR
|
FIR07-00305
| INSP-Final Inspection | 12/11/2007 | 12/13/2007 | 12/13/2007 3:08:47 PM | P | FAIL |
|
|
Fire dampers on 2nd and 3rd floor do not close all the way.KR
|
FIR07-00980
| INSP-Final Inspection | 12/13/2007 | 12/13/2007 | 12/13/2007 1:07:44 PM | P | PASS |
|
|
Scope of work completed.KR
|
BLD07-03062
| FIRE-Final Inspection | 12/12/2007 | 12/13/2007 | 12/13/2007 10:23:35 AM | A | FAIL |
|
|
Repair the exit signs and emergency lights, provide sticker at the main exit, install the hood, hood suppression system and fire alarm interconnection. All of this work requires separate permits. Provide permit for the fire sprinkler work that needs done such as the sprinkler head that is too close to the wall and protection in the cooler that has not been installed yet. Provide fire extinguishers. Provide lever hardware on the restroom door.
|
BLD07-02535
| FIRE-Final Inspection | 12/12/2007 | 12/13/2007 | 12/13/2007 9:52:25 AM | A | FAIL |
|
|
Provide tags for the fire extinguishers and spring hinges for the 201 apartment door.
|
FIR07-00761
| INSP-Final Inspection | 12/12/2007 | 12/13/2007 | 12/13/2007 8:44:48 AM | A | FAIL |
|
|
robert Phone #: ###-#### Could not contact the general contractor by phone or at the job site. Per the works he was sleeping in.
|
FIR07-00637
| INSP-Sprinkler Rough-in/Hydro | 12/11/2007 | 12/13/2007 | 12/13/2007 8:44:03 AM | A | CANC |
|
|
Per Nate this is for a hydro test which can not be done due to a head leaking that needs replaced.
|