Inspections for the day of: Thursday, December 13, 2007.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00816 INSP-Sprinkler Rough-in/Hydro12/12/200712/13/200712/13/2007 4:27:38 PMPFAIL
Hydro test passed. Backflow needs to be certified,loading dock on north side of building with awning needs to be covered w/sprinkler,sprinkler head in wharehouse office needs tape removed.KR
FIR07-00770 INSP-Final Inspection12/12/200712/13/200712/13/2007 3:49:55 PMAFAIL
I arrived at the scheduled 8:00am and found tim but no heating guy. I left and returned at 11:45am. After testing four of the five duct smoke detectors in the open sales area, one duct detector was found inoperative. The test was stopped due to time constraints.
FIR07-00761 INSP-Final Inspection12/13/200712/13/200712/13/2007 3:34:09 PMPPASS
Sprinkler permit for this scope of work finaled.KR
FIR07-00736 INSP-Final Inspection12/12/200712/13/200712/13/2007 3:11:09 PMAPASS
Test areas that we could not test during last inspection for this permit #..KR
FIR07-00305 INSP-Final Inspection12/11/200712/13/200712/13/2007 3:08:47 PMPFAIL
Fire dampers on 2nd and 3rd floor do not close all the way.KR
FIR07-00980 INSP-Final Inspection12/13/200712/13/200712/13/2007 1:07:44 PMPPASS
Scope of work completed.KR
BLD07-03062 FIRE-Final Inspection12/12/200712/13/200712/13/2007 10:23:35 AMAFAIL
Repair the exit signs and emergency lights, provide sticker at the main exit, install the hood, hood suppression system and fire alarm interconnection. All of this work requires separate permits. Provide permit for the fire sprinkler work that needs done such as the sprinkler head that is too close to the wall and protection in the cooler that has not been installed yet. Provide fire extinguishers. Provide lever hardware on the restroom door.
BLD07-02535 FIRE-Final Inspection12/12/200712/13/200712/13/2007 9:52:25 AMAFAIL
Provide tags for the fire extinguishers and spring hinges for the 201 apartment door.
FIR07-00761 INSP-Final Inspection12/12/200712/13/200712/13/2007 8:44:48 AMAFAIL
robert Phone #: ###-#### Could not contact the general contractor by phone or at the job site. Per the works he was sleeping in.
FIR07-00637 INSP-Sprinkler Rough-in/Hydro12/11/200712/13/200712/13/2007 8:44:03 AMACANC
Per Nate this is for a hydro test which can not be done due to a head leaking that needs replaced.