Inspections for the day of: Monday, December 13, 2010.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE10-02755 Electrical Rough-In12/13/201012/13/201012/13/2010 3:17:42 PMPPASS
>> Inspection requested via web by Terry Scott ri ok
ELE09-01364 Final12/13/201012/13/201012/13/2010 3:00:31 PMPPASS
ok final
ELE10-02754 Permanent Service12/13/201012/13/201012/13/2010 2:40:28 PMPFAIL
Please call for any questions, thanks, Terry W. Phone #: ###-#### >> Inspection requested via web by Stephen Kren called, left correction notice, NEC 110.26 shall provide workspace about service, 110.12(A) unused openings shall be closed, 250.24 shall ground ac service at point of grounded service conductor termination, 250.52(A)(1) shall provide metal underground water pipe as main grounding electrode and augment with 2 ground rods 6' apart, 314.15 fittings shall be listed for use in wet locations, BCC no violations shall be retained,
ELE10-02401 Permanent Service12/13/201012/13/201012/13/2010 1:30:03 PMPPASS
Call Steve if u need access into tenants Phone #: ###-#### >> Inspection requested via web by steve sellers p/s, exst meter pak, rec, ok, 1 meter only req'd
ELE10-01893 ELE-Aging Inspection12/13/201012/13/201012/13/2010 10:33:15 AM DONE
suc
ELE10-01869 ELE-Aging Inspection12/13/201012/13/201012/13/2010 10:11:12 AM DONE
see final
ELE10-01869 Final12/13/201012/13/201012/13/2010 10:10:46 AMAPASS
ok
ELE10-02455 Electrical Rough-In12/9/201012/13/201012/13/2010 9:52:54 AMAPASS
Karen Phone #: ###-#### ok cover floor heat
ELE10-02752 Electrical Rough-In12/13/201012/13/201012/13/2010 9:20:47 AMAPASS
Will be ready for inspection after 9 please give me half an hour notice so that I can meet you there thanks Shaun ###-#### Phone #: ###-#### >> Inspection requested via web by Shaun Kirkman ri ok
ELE10-02752 Final12/13/201012/13/201012/13/2010 9:20:38 AMAPASS
Will be ready for inspection after 9 please give me half an hour notice so that I can meet you there thanks Shaun ###-#### Phone #: ###-#### >> Inspection requested via web by Shaun Kirkman ok final