FIR10-00309
| FIR-Aging Inspection | 12/13/2010 | 12/13/2010 | 12/16/2010 1:06:51 PM | | NR |
|
|
Per Mike this permit will be called in for inspection for tomorrow afternoon.
|
FIR08-00418
| FIR-Aging Inspection | 12/13/2010 | 12/13/2010 | 12/16/2010 1:00:14 PM | | NR |
|
|
Per Jim Danes this work will be finished when another permit in this same building is called in for an inspection possibly next week.
|
FIR10-00033
| FIR-Aging Inspection | 12/13/2010 | 12/13/2010 | 12/16/2010 12:58:50 PM | | NR |
|
|
Per Charlie this permit will be addressed
|
BLD10-02796
| FIRE-Final Inspection | 12/13/2010 | 12/13/2010 | 12/14/2010 10:33:35 AM | P | FAIL |
|
|
Provide single action hardware on all of the exterior doors, remove deadbolts, and lower and tag the existing fire extinguisher. Per Terry Records the addressing at this building is ok.
|
FIR10-00626
| INSP-Sprinkler Rough-in | 12/13/2010 | 12/13/2010 | 12/13/2010 4:09:49 PM | P | CANC |
|
|
Cancelled due to time constraints. Rescheduled for tomorrow.
|
FIR10-00424
| INSP-Final Inspection | 12/13/2010 | 12/13/2010 | 12/13/2010 4:07:58 PM | P | FAIL |
|
|
The NAC circuit did not report a trouble to the FACP. The FACP did not report a trouble to the monitoring station and did not activate a trouble signal at the remote annunciator. This is a requirement of NFPA 72 4.4.7.1. The sprinkler tamper switches reported a toruble signal at the remote annunciator and at the monitoring station. The lenses of the new strobes are not mounted between 80" and 96". Also as-builts are needed which show all of the existing a/v's remaining on the existing panel and only the three new a/v's being added to the new NAC panel. Revised EOL voltage drop calculations are needed and battery calculations are needed. There was no actual testing of devices.
|
BLD10-00987
| FIRE-Final Inspection | 12/10/2010 | 12/13/2010 | 12/13/2010 3:47:56 PM | A | CANC |
|
|
The project related fire alarm and fire sprinkler permits were not ready for inspection.
|
FIR10-00470
| INSP-Final Inspection | 12/10/2010 | 12/13/2010 | 12/13/2010 3:36:48 PM | A | CANC |
|
|
Rescheduled for tomorrow. Bill did not have the pito guage for the forward flow test and the fire alarm permit had not been called in for the testing of the fire alarm/fire sprinkler interconnections.
|
FIR10-00218
| INSP-Final Inspection | 12/8/2010 | 12/13/2010 | 12/13/2010 11:32:14 AM | A | PASS |
|
|
Permit finaled
|