ELE11-02562
| Permanent Service | 12/13/2011 | 12/13/2011 | 12/13/2011 2:53:55 PM | P | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by Neal Rumsey NEC Table 250.66 Water pipe bond shall be 2/0 cu. or 4/0 alu
|
ELE11-02770
| Temporary Service | 12/13/2011 | 12/13/2011 | 12/13/2011 1:31:20 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Alan Lusk t/s u/g n ok
|
ELE11-02769
| Temporary Service | 12/13/2011 | 12/13/2011 | 12/13/2011 1:19:18 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Alan Lusk t/s u/g n ok
|
ELE11-02794
| Final | 12/13/2011 | 12/13/2011 | 12/13/2011 1:12:55 PM | P | PASS |
|
|
final ok
|
ELE11-02794
| Electrical Rough-In | 12/13/2011 | 12/13/2011 | 12/13/2011 1:12:31 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Stuart Welton rough-in ok cover Hot tub circuit, UL listing Garage circuits
|
ELE11-02788
| Electrical Rough-In | 12/13/2011 | 12/13/2011 | 12/13/2011 10:08:07 AM | P | PASS |
|
|
Contact: Garrett Collins, ufer ground inspection please Phone #: ###-#### >> Inspection requested via web by Deb Gooden rough-in ok cover concrete encased electrode Walgreens
|
ELE11-02776
| Electrical Rough-In | 12/12/2011 | 12/13/2011 | 12/13/2011 9:43:06 AM | A | PASS |
|
|
Contact Craig Timmons with any questions. Phone #: ###-#### >> Inspection requested via web by Tina Payne rough-in ok cover walls five rooms/ two areas
|
ELE11-02792
| Final | 12/13/2011 | 12/13/2011 | 12/13/2011 9:19:26 AM | P | NR |
|
|
Increased 100 amp service to 200 amps. Phone #: ###-#### >> Inspection requested via web by Dan Mitchell Not ready till 12/14/2011
|
ELE11-02777
| Electrical Rough-In | 12/12/2011 | 12/13/2011 | 12/13/2011 9:12:04 AM | A | PASS |
|
|
Wall Cover >> Inspection requested via web by Tyler Bowen rough-in ok cover walls
|
ELE11-02689
| Final | 12/12/2011 | 12/13/2011 | 12/13/2011 8:53:07 AM | A | PASS |
|
|
steve Phone #: ###-#### final ok Electical contractor will install panel directory 12/13/2011
|
ELE11-01944
| Final | 12/12/2011 | 12/13/2011 | 12/13/2011 8:29:21 AM | A | NR |
|
|
Phone #: ###-#### >> Inspection requested via web by Paul Young Not ready NEC 330.(B) Need to support MC cable
|
ELE11-02537
| Final | 12/12/2011 | 12/13/2011 | 12/12/2011 1:30:20 PM | A | PASS |
|
|
Please provide electrical final inspection for tennant improvement.
Call Dave Mackey with questions or access to building Phone #: ###-#### >> Inspection requested via web by David Mackey final ok
|