Inspections for the day of: Thursday, December 13, 2012.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE11-02682 ELE-Aging Inspection12/13/201212/13/201212/13/2012 1:34:34 PM DONE
Confirmed job finished
ELE11-02682 Final12/13/201212/13/201212/13/2012 1:33:53 PMPPASS
Final ok
ELE12-01639 Final12/12/201212/13/201212/13/2012 1:23:23 PMPFAIL
Contact is Jason. Final on house addition. Phone #: ###-#### >> Inspection requested via web by Buster Bowen
NEC 410.16(C) Incandescent luminaire shall be located a minimum of 12" from storage space or shelf.
NEC 440.6 Ampacity of AC unit name plate rating 20 amp max. 30 amp breaker installed.
NEC 406(B) Back patio receptical shall be weather resistant type.
ESC12-01129 Site Preparation12/13/201212/13/201212/13/2012 12:52:57 PM PASS
Perimeter sediment fence in place. Have not broke ground yet. ESC sign posted.
ELE12-03013 Temporary Service12/12/201212/13/201212/13/2012 12:05:59 PMPPASS
Let me know if there are any problems. Thanks Phone #: ###-#### >> Inspection requested via web by Clay Morgan t/s o/h n ok
ELE11-02678 ELE-Aging Inspection12/13/201212/13/201212/13/2012 10:24:40 AM DONE
Contacted contractor who will make contact with owner
ELE11-02690 ELE-Aging Inspection12/13/201212/13/201212/13/2012 10:18:05 AM DONE
Made contact with contractor and drove by
ELE11-02690 Final12/13/201212/13/201212/13/2012 10:17:32 AMPPASS
Final ok
ELE12-02707 Final12/13/201212/13/201212/13/2012 9:36:28 AMAPASS
please call me if house is locked for key location
Thanks Bob Phone #: ###-#### >> Inspection requested via web by Julie Schroder Final ok
ELE12-02978 Final12/12/201212/13/201212/13/2012 9:24:49 AMAPASS
Please call Jamie Winters ###-#### before going so we can be present Phone #: ###-#### >> Inspection requested via web by Lori Stout Final ok
ELE12-02977 Final12/12/201212/13/201212/13/2012 9:23:49 AMAPASS
Pleae call Jamie Winters ###-#### so we can be present Phone #: ###-#### >> Inspection requested via web by Lori Stout Final ok
ELE12-02976 Final12/12/201212/13/201212/13/2012 9:22:47 AMAPASS
Please call Jamie Winters ###-#### before going so we can be present Phone #: ###-#### >> Inspection requested via web by Lori Stout Final ok
ELE12-00290 Final12/12/201212/13/201212/13/2012 9:16:45 AMAPASS
Please call Jamie Winters ###-#### before going so we can be present Phone #: ###-#### >> Inspection requested via web by Lori Stout Final ok
ELE12-00235 Electrical Rough-In12/12/201212/13/201212/12/2012 2:04:24 PMACANC
Please inspect basement media room for rough-in. Access through side gate and back slider door. Phone #: ###-#### >> Inspection requested via web by ERIC CENTERS Inspection cancelled from web by: ERIC CENTERS