FIR12-00483
| INSP-Final Inspection | 12/13/2012 | 12/13/2012 | 12/14/2012 2:27:45 PM | P | FAIL |
|
|
Still waiting on ceiling tile to be installed. I also noted that several upright heads near the front of the building appear to be painted and other heads at the center of the building still have tin foil on them. I spoke to Dave about these items. I also spoke to Cole and asked him to reschedule a final for Monday.
|
MIS12-00344
| BLD-Conference | 12/13/2012 | 12/13/2012 | 12/14/2012 9:21:42 AM | P | DONE |
|
|
I spoke to Mike Jordan and Jeremy with Boise Fire about the outstanding issues.
|
FIR12-00640
| INSP-Alarm Testing | 12/12/2012 | 12/13/2012 | 12/13/2012 4:03:49 PM | P | DONE |
|
|
Provide accurate as-builts, provide breaker locks, provide map at the facp, provide shutdown/reduction of music/arcade machines as per NFPA 72 18.4.1.5, 18.4.3.5, relocate smoke detector to the deck at the facp. Signals verified for flow and tamper switches, hvac reporting and shutdown and kitchen hood suppression systems. Spacing verified for audio/visual devices. EOL verified as ok.
|
FIR12-00609
| INSP-Final Inspection | 12/12/2012 | 12/13/2012 | 12/13/2012 3:58:52 PM | P | FAIL |
|
|
When testing the first hood I found that the lights under the hood did not shut off. Gas and power to the equipment did shut off. Contractor agreed to provide shutoff for lights and then reschedule.
|
BLD12-02304
| FIRE-Conference | 12/13/2012 | 12/13/2012 | 12/13/2012 3:46:28 PM | P | DONE |
|
|
I met Randy with Shilo on site and went over the locations where I had found overspaced upright sprinkler heads.
|
FIR12-00665
| INSP-Sprinkler Rough-in/Hydro | 12/11/2012 | 12/13/2012 | 12/13/2012 3:44:15 PM | A | PASS |
|
|
underground hydro & flush passed
|
BLD12-03186
| FIRE-Final Inspection | 12/12/2012 | 12/13/2012 | 12/13/2012 10:27:45 AM | A | FAIL |
|
|
Provide for current inspection for the fire extinguisher and either repair or remove the exit sign out of the back door.
|
BLD12-03154
| FIRE-Conference | 12/12/2012 | 12/13/2012 | 12/13/2012 10:10:26 AM | A | DONE |
|
|
Doug will need an Occupancy Permit for people to move in, sprinkler modifications, fire alarm modifications and passage hardware at the island restroom doors as per the approved plans.
|
FIR12-00585
| INSP-Final Inspection | 12/12/2012 | 12/13/2012 | 12/13/2012 9:26:38 AM | A | PASS |
|
|
Permit finaled. Test was performed by "shorting" the wires at the pressure switch. The appliance has a UL label and a built in fire suppression system. Per installer the entire suppression system would need to be replaced if a functional test was required.
|