Inspections for the day of: Wednesday, December 13, 2017.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorEric Story
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-04170 Conference12/12/201712/13/201712/13/2017 3:01:08 PMPDONE
Bill Phone #: ###-####-would like you to call him with an approx. time so he can meet you there
Disscused raising mast of meter and not to exceed 6' due to IDPCO
ELE17-04189 Rough-In Permanent Service12/13/201712/13/201712/13/2017 2:31:58 PMPPASS
Request the inspection after 1:00 today if possible thank you Phone #: ###-#### Inspection requested via web by Brad Baker
Rough-in only at this time, need avalaible fault calc done proir to service being energized, Building ok to cover
ELE17-02307 Electrical Rough-In12/12/201712/13/201712/13/2017 1:20:36 PMPPASS
Floor heat inspection for kitchen only. Phone #: ###-#### Inspection requested via web by Garrett Collins
Kitchen floor heat only ok to cover
ELE17-03106 Final12/12/201712/13/201712/13/2017 12:36:10 PMPPASS
Phone #: ###-#### Inspection requested via web by A.M.E. Office
Yert final ok
ELE17-03811 Conference12/11/201712/13/201712/13/2017 10:51:05 AMADONE
electrical contractor would like to meet with electrical inspector for verification on corrections needing done. 9;30 am is the best time please let me know 1/2 hour before arriving. Phone #: ###-#### Inspection requested via web by SHAWN TOMLINSON
Discussed corrections given on previous inspections, wall will be reframed for clearences and all corections have been addressed and will have a reinspection on another date once completed.
ELE17-04039 Final12/12/201712/13/201712/13/2017 9:15:10 AMACANC
Panel in the garage. My work is five minutes away. Phone #: ###-#### Inspection requested via web by Gail Hofert
Needed conference
ELE17-04039 Conference12/13/201712/13/201712/13/2017 9:15:02 AMPPASS
Panel in the garage. My work is five minutes away. Phone #: ###-#### Inspection requested via web by Gail Hofert
Owner did service change and needs to establish grounding proir to service being energized, will add 2 grounds and have a permanent inspection once completed.
ELE17-04053 Electrical Rough-In12/12/201712/13/201712/13/2017 8:52:41 AMACANC
First thing in the morming for back baths rough-in
Walls and hard lids in bath's ok to cover.