ELE18-03283
| Conference | 12/12/2018 | 12/13/2018 | 12/13/2018 5:11:15 PM | A | DONE |
|
|
Don will be on job site after 9:30 Phone #: ###-#### Inspection requested via web by Terry Scott. Scope of existing electrical permit does not cover pool area. The repair of the damaged underground conductors to the pool equipment and additional new branch circuit for hot tub descriptions and fees are required to added to the existing electrical permit or a new permit may be obtained. 2017 NEC will apply.
|
ELE18-04672
| Electrical Rough-In | 12/13/2018 | 12/13/2018 | 12/13/2018 1:59:08 PM | P | PASS |
|
|
Re-inspect detached shed for nail plates and staples. Phone #: ###-#### Inspection requested via web by Jonathan Poot correction done, rough-in ok cover
|
ELE18-04296
| Final | 12/12/2018 | 12/13/2018 | 12/13/2018 1:36:48 PM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Jonathan Poot NEC 440.6 Maximum overcurrent protection from unit name plate shall be 15 ampere, 20 ampere breaker has been installed.
|
ELE18-03806
| Final | 12/12/2018 | 12/13/2018 | 12/13/2018 10:43:15 AM | A | PASS |
|
|
Garage code 7373 Phone #: ###-#### Inspection requested via web by Heath Thomas final ok
|
ELE18-04672
| Electrical Rough-In | 12/12/2018 | 12/13/2018 | 12/13/2018 9:48:50 AM | A | PART |
|
|
Phone #: ###-#### Inspection requested via web by Jonathan Poot rough-in ok cover dinning room addition only, no cover for detached NEC 300.4 NM cable shall not be secured with-in 1 1/4 of framing member edge
|
ELE18-02554
| Final | 12/11/2018 | 12/13/2018 | 12/13/2018 8:42:57 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Katie Sitterle job complete, final ok
|
ELE18-04494
| Electrical Rough-In | 12/12/2018 | 12/13/2018 | 12/13/2018 8:20:49 AM | A | PASS |
|
|
Ceiling Phone #: ###-#### Inspection requested via web by Kevin Burke rough-in ok cover ceiling grid back room
|