Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00740 INSP-Final Inspection12/10/200412/14/200412/14/2004 12:00:00 AMAFAIL
Signals for the initiating devices did not go out, duct detectors did not shut down hvac units, provide additional a/v in the dry cleaners since wall that is not shown on the plans blocks coverage 12/14/2004 11:27:26 AM
FIR04-00625 INSP-Final Inspection12/10/200412/14/200412/14/2004 12:00:00 AMAFAIL
There appears to be people living in the basement. Plans submitted and approved do not address a residential occupancy. Resubmit plans addressing a residential occupancy. 12/14/2004 12:16:29 PM
FIR04-00546 INSP-Conference12/13/200412/14/200412/14/2004 12:00:00 AMAPASS
Sprinkler piping in the central corridor is ok to cover 12/14/2004 8:34:40 AM
FIR04-00564 INSP-Supply line flush12/13/200412/14/200412/14/2004 12:00:00 AMAPASS
Underground supply piping flushed 12/14/2004 8:32:42 AM
FIR04-00552 INSP-Sprinkler Rough-in12/13/200412/14/200412/14/2004 12:00:00 AMAPART
Sprinkler rough-in is passed for the overhead system. Underground has not been verified. Tenting is ok except for the entry/central corridor area which was not complete yet. 12/14/2004 11:40:02 AM
FIR04-00722 INSP-Sprinkler Rough-in/Hydro12/14/200412/14/200412/14/2004 12:00:00 AMPPASS
Fire sprinkler finaled 12/14/2004 2:46:54 PM
BLD04-01993 FIRE-Final Inspection12/14/200412/14/200412/14/2004 12:00:00 AMPFAIL
Provide occupant load sign and provide one additional fire extinguisher within 75' of the southwest corner of the dining area 12/14/2004 2:48:09 PM
BLD04-01016 FIRE-Final Inspection12/9/200412/14/200412/14/2004 12:00:00 AMPCANC
keith; Phone #: ###-#### Internet Inspection Request from: Barbara Moore per Keith cancel reset for 12/16 JRR
FIR04-00681 INSP-Final Inspection12/10/200412/14/200412/14/2004 12:00:00 AMPPASS
Fire alarm finaled 12/15/2004 8:17:11 AM
FIR04-00681 INSP-Final Inspection12/10/200412/14/200412/14/2004 12:00:00 AMPPASS
Fire alarm finaled 12/15/2004 8:17:11 AM