ELE05-04504
| Final | 12/14/2005 | 12/14/2005 | 12/14/2005 7:39:13 PM | P | NR |
|
|
###-#### - chuck called contr, needs to finish
|
ELE05-04322
| Final | 12/14/2005 | 12/14/2005 | 12/14/2005 4:01:18 PM | P | PASS |
|
|
PLEASE CALL MORGAN 20 MINUTES AHEAD OF TIME SO HE CAN LET YOU IN BUILDING; Phone #: ###-#### Internet Inspection Request from: Tyler Bowen ok to final
|
ELE05-03956
| Final | 12/14/2005 | 12/14/2005 | 12/14/2005 4:00:36 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 12/14/2005 at 8:24:44 AM. Contact: ###-####. ok to final
|
ELE05-04505
| Rough-In Permanent Service | 12/14/2005 | 12/14/2005 | 12/14/2005 2:44:30 PM | P | FAIL |
|
|
jack ###-#### called contr, left corr notice, 300.4(A) &(D) edgeof bored hole and nm cable shall be 1 1/4" from edge of framing member,110.12(A) unused openings in box shall be closed,110.12(C) cable jacket shall not be damaged,725.55(A) cl 2&3 cable shall not be run with cl 1cable,cable shall not be looped under joist, BCC address shall be posted, approved set of plans shall be on job
|
ELE05-04323
| Electrical Rough-In | 12/12/2005 | 12/14/2005 | 12/14/2005 2:32:32 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 12/12/2005 at 7:45:01 AM. Contact: ###-####. soffits ok to cover
|
ELE05-04236
| Final | 12/13/2005 | 12/14/2005 | 12/14/2005 12:28:57 PM | P | CANC |
|
|
Scheduled by a contractor via Hello! on 12/13/2005 at 10:25:43 PM. Contact: ###-####. see ri
|
ELE05-04322
| Final | 12/12/2005 | 12/14/2005 | 12/14/2005 10:11:25 AM | A | NH |
|
|
MORGAN; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy called contr, said to call back so can sign card
|
ELE03-03039
| ELE-Aging Inspection | 12/14/2005 | 12/14/2005 | 12/14/2005 10:09:33 AM | | PASS |
|
|
see final for ele03-03037, ok to final
|
ELE05-04024
| Electrical Rough-In | 12/12/2005 | 12/14/2005 | 12/14/2005 9:52:35 AM | A | PASS |
|
|
Ceiling inspection for cover, please.; Phone #: ###-#### Internet Inspection Request from: Tawnya McKinney ok to cover clg, told elect to blank off exst clg mtd recpts, and to verify listings for equip
|
ELE05-04500
| Electrical Rough-In | 12/13/2005 | 12/14/2005 | 12/14/2005 9:23:50 AM | A | PASS |
|
|
###-#### - brian walls only ok to cover
|
ELE05-04501
| Electrical Rough-In | 12/13/2005 | 12/14/2005 | 12/14/2005 9:23:11 AM | A | PASS |
|
|
###-#### - brian walls and ceiling ok to cover
|
ELE05-01293
| Electrical Rough-In | 12/13/2005 | 12/14/2005 | 12/14/2005 8:20:17 AM | A | PASS |
|
|
ceiling inspection please///jerimiah; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok to cover foyer ceiling
|
ELE03-03039
| Final | 12/14/2005 | 12/14/2005 | 12/14/2005 12:00:00 AM | P | PASS |
|
|
equip and project finalled 11-07-05. ok to final
|
ELE05-04236
| Electrical Rough-In | 12/14/2005 | 12/14/2005 | 12/14/2005 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 12/13/2005 at 10:25:43 PM. Contact: ###-####. ok to cover ceiling, will do final ltr
|