Inspections for the day of: Wednesday, December 14, 2005.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD05-02963 FIRE-Final Inspection12/14/200512/14/200512/15/2005 10:47:23 AMPPASS
Fire life safety passed inspection.
FIR05-00659 INSP-Sprinkler Rough-in/Hydro12/14/200512/14/200512/15/2005 9:55:20 AMPFAIL
The overhead hydrostatic test for the new refrigerated storage area passed, rough-in for this area needs flexible couplings installed where 6" main passes through the wall, verification that the 6" main can be supported by a single truss as installed, some upright heads are blocked by close proximity to metal truss webs not meeting min. distance requirements from these types of obstructions per NFPA 13 8.6.5.2.1.7.
BLD05-01478 FIRE-Final Inspection12/13/200512/14/200512/14/2005 12:15:23 PMPNR
Fire alarm and fire sprinkler must be inspected and approved prior to life safety final.
BLD04-02409 FIRE-Final Inspection12/13/200512/14/200512/14/2005 12:14:36 PMPNR
Fire alarm and fire sprinkler must be inspected and approved prior to life safety final.
FIR05-00385 INSP-Sprinkler Rough-in/Hydro12/13/200512/14/200512/14/2005 12:13:40 PMPDONE
This duplicate inspection already called in has been completed, see c/n items listed.
BLD05-01480 FIRE-Final Inspection12/13/200512/14/200512/14/2005 12:12:30 PMANR
Fire alarm and fire sprinkler must be inspected and approved prior to life safety final.
FIR05-00385 INSP-Sprinkler Rough-in/Hydro12/13/200512/14/200512/14/2005 12:10:56 PMAPART
Retest of the preaction system hydrostatic two hour test passed.
FIR05-00385 INSP-Sprinkler Rough-in12/13/200512/14/200512/14/2005 12:09:37 PMAPART
Overhead is acceptable pending installation of missing escutcheons, ceiling tile, remove tape and paper at uprights where covered for painting, need heads in head box and wrench, perform forward flow, alarms, sign at bell.
BLD05-01279 FIRE-Final Inspection12/13/200512/14/200512/14/2005 9:33:46 AMAPASS
c/n items have been completed as requested, inspection passed.