BLD05-02963
| FIRE-Final Inspection | 12/14/2005 | 12/14/2005 | 12/15/2005 10:47:23 AM | P | PASS |
|
|
Fire life safety passed inspection.
|
FIR05-00659
| INSP-Sprinkler Rough-in/Hydro | 12/14/2005 | 12/14/2005 | 12/15/2005 9:55:20 AM | P | FAIL |
|
|
The overhead hydrostatic test for the new refrigerated storage area passed, rough-in for this area needs flexible couplings installed where 6" main passes through the wall, verification that the 6" main can be supported by a single truss as installed, some upright heads are blocked by close proximity to metal truss webs not meeting min. distance requirements from these types of obstructions per NFPA 13 8.6.5.2.1.7.
|
BLD05-01478
| FIRE-Final Inspection | 12/13/2005 | 12/14/2005 | 12/14/2005 12:15:23 PM | P | NR |
|
|
Fire alarm and fire sprinkler must be inspected and approved prior to life safety final.
|
BLD04-02409
| FIRE-Final Inspection | 12/13/2005 | 12/14/2005 | 12/14/2005 12:14:36 PM | P | NR |
|
|
Fire alarm and fire sprinkler must be inspected and approved prior to life safety final.
|
FIR05-00385
| INSP-Sprinkler Rough-in/Hydro | 12/13/2005 | 12/14/2005 | 12/14/2005 12:13:40 PM | P | DONE |
|
|
This duplicate inspection already called in has been completed, see c/n items listed.
|
BLD05-01480
| FIRE-Final Inspection | 12/13/2005 | 12/14/2005 | 12/14/2005 12:12:30 PM | A | NR |
|
|
Fire alarm and fire sprinkler must be inspected and approved prior to life safety final.
|
FIR05-00385
| INSP-Sprinkler Rough-in/Hydro | 12/13/2005 | 12/14/2005 | 12/14/2005 12:10:56 PM | A | PART |
|
|
Retest of the preaction system hydrostatic two hour test passed.
|
FIR05-00385
| INSP-Sprinkler Rough-in | 12/13/2005 | 12/14/2005 | 12/14/2005 12:09:37 PM | A | PART |
|
|
Overhead is acceptable pending installation of missing escutcheons, ceiling tile, remove tape and paper at uprights where covered for painting, need heads in head box and wrench, perform forward flow, alarms, sign at bell.
|
BLD05-01279
| FIRE-Final Inspection | 12/13/2005 | 12/14/2005 | 12/14/2005 9:33:46 AM | A | PASS |
|
|
c/n items have been completed as requested, inspection passed.
|