Inspections for the day of: Wednesday, December 14, 2005.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00582 FIR-Aging Inspection12/14/200512/14/200512/15/2005 11:37:13 AM NR
Work in progress
BLD05-01910 FIRE-Final Inspection12/13/200512/14/200512/14/2005 1:32:51 PMPFAIL
Repair the south emergency light, provide sticker at door, provide indicator at keyed exterior exit door. Duct smoke detectors not required. Contractor still needs to get the 5" outlet of the fire hydrant turned towards the driveway.
BLD04-01822 FIRE-Final Inspection12/13/200512/14/200512/14/2005 1:32:38 PMPFAIL
Repair the south emergency light, provide sticker at door, provide indicator at keyed exterior exit door. Duct smoke detectors not required. Contractor still needs to get the 5" outlet of the fire hydrant turned towards the driveway.
BLD05-02350 FIRE-Final Inspection12/13/200512/14/200512/14/2005 1:29:27 PMAPASS
Life safety finaled
BLD04-02346 FIRE-Conference12/13/200512/14/200512/14/2005 1:27:40 PMADONE
I spoke to Mike about the requirement for a sprinkler head at the top of the elevator shaft. I referred him to NFPA 13 and its non requirement if shaft is non-combustible and the elevator meets ANSI 17.1
FIR05-00739 INSP-Final Inspection12/13/200512/14/200512/14/2005 1:25:57 PMAPASS
Permit finaled.
BLD05-02852 FIRE-Final Inspection12/13/200512/14/200512/14/2005 1:24:53 PMAPASS
Permit finaled
FIR04-00207 INSP-Final Inspection12/13/200512/14/200512/14/2005 1:24:01 PMAPASS
Permit finaled
FIR05-00198 INSP-Final Inspection12/13/200512/14/200512/14/2005 1:23:41 PMAFAIL
Horns and strobes not sync'd. Need nfpa 72 forms and to verify signals.