Inspections for the day of: Thursday, December 14, 2006.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00902 INSP-Sprinkler Rough-in12/14/200612/14/200612/15/2006 1:09:38 PMPPART
Fire sprinkler rough-in is approved for cover at the drop ceilings, final pending tile and escutcheons.
BLD06-00028 FIRE-Final Inspection12/13/200612/14/200612/15/2006 12:33:03 PMPPASS
Life safety inspection passed.
BLD06-01211 FIRE-Final Inspection12/14/200612/14/200612/14/2006 3:05:59 PMPFAIL
Provide building address. Also discussed requirements for occupancy at the TI phase.
BLD06-01893 FIRE-Final Inspection12/14/200612/14/200612/14/2006 3:03:24 PMANR
Pending project related fire alarm permit final.
FIR06-00746 INSP-Final Inspection12/13/200612/14/200612/14/2006 3:02:51 PMPFAIL
Notification devices are overspaced or lacking at some areas as noted, need to program duct detection devices for HVAC shutdown, will need to test the remainder of work for the shell permit including the elevator controls prior to occupancy for this tenant.
BLD06-01188 FIRE-Final Inspection12/11/200612/14/200612/14/2006 2:54:54 PMPFAIL
Missing one row of fire sprinkler heads at the transition between the SE and SW quadrants, door hardware at the two restrooms in the NE quad is not approved, need to provide additional emergency lighting at the exits to the NW stair tower.
BLD05-00802 FIRE-Final Inspection12/14/200612/14/200612/14/2006 2:51:58 PMPPASS
Items on previous c/n have been completed, life safety inspection passed.
FIR06-00876 INSP-Final Inspection12/14/200612/14/200612/14/2006 2:50:14 PMPPASS
Fire sprinkler permit finaled.
FIR05-00772 INSP-Supply line flush12/13/200612/14/200612/14/2006 11:54:03 AMAPART
UG fire supply line flush completed.
FIR06-00768 INSP-Final Inspection12/13/200612/14/200612/14/2006 10:15:45 AMAPASS
Fire sprinkler permit finaled.
FIR06-00671 INSP-Supply line flush12/13/200612/14/200612/14/2006 10:15:12 AMACANC
Per phone call from contractor, not ready for inspection, to be rescheduled.
FIR06-00769 INSP-Final Inspection12/13/200612/14/200612/14/2006 10:14:04 AMAPASS
Fire alarm permit finaled.
BLD06-02129 FIRE-Final Inspection12/13/200612/14/200612/14/2006 10:13:32 AMAPASS
Items on c/n have been completed, fire life safety inspection passed.