Inspections for the day of: Thursday, December 14, 2006.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD05-00635 FIRE-Final Inspection12/14/200612/14/200612/15/2006 9:28:30 AMPPART
A temporary occupancy was given until the fire alarm permit has been finaled, the grading permit is finaled and the temporary exit discharge light located at the east exit has been replaced with the permanent fixture.
FIR05-00836 INSP-Final Inspection12/14/200612/14/200612/15/2006 9:25:31 AMPPART
A temporary occupancy is being given on this fire alarm permit until the 2nd floor NAC panel has been tested and the as-built fire alarm plans have been resubmitted.
FIR06-00526 INSP-Sprinkler Rough-in/Hydro12/14/200612/14/200612/14/2006 12:40:14 PMPFAIL
Hydro test failed. Leaking at heads.
BLD06-02890 FIRE-Final Inspection12/13/200612/14/200612/14/2006 12:39:31 PMACANC
Wrong inspection number called in.
BLD06-02317 FIRE-Final Inspection12/13/200612/14/200612/14/2006 11:51:35 AMAPASS
Fire life safety finaled
BLD06-02317 FIRE-Alarm Testing12/13/200612/14/200612/14/2006 11:51:17 AMAPASS
The access controled egress door functioned correctly
FIR06-00564 INSP-Supply line flush12/14/200612/14/200612/14/2006 10:58:30 AMAPASS
Underground supply piping is ok to cover. I notified the fire sprinkler contractor that the PIV will be required to be electronically supervised and that it would be a good idea to install the conduit in the open trench prior to bury.
FIR06-00843 INSP-Sprinkler Rough-in/Hydro12/14/200612/14/200612/14/2006 10:40:29 AMAPASS
Tenting inspection passed. Piping is ok to cover.
BLD06-01634 FIRE-Final Inspection12/13/200612/14/200612/14/2006 10:16:34 AMAPASS
Permit finaled
BLD06-03005 FIRE-Final Inspection12/13/200612/14/200612/14/2006 9:44:07 AMAPASS
Life safety finaled
FIR06-00623 INSP-Sprinkler Rough-in12/13/200612/14/200612/14/2006 9:12:12 AMAPART
Piping is ok to cover. One attic pendant head has not been installed and the attic pendant heads install on the 4" main at the riser are too far from the insulation. See city approved plans for locations. Contractor states access will be provided to verify these items later.
BLD06-01554 FIRE-Final Inspection12/14/200612/14/200612/14/2006 9:09:39 AMPPASS
Life safety finaled
FIR06-00750 INSP-Final Inspection12/13/200612/14/200612/14/2006 9:09:24 AMAPASS
Permit finaled
BLD06-02356 FIRE-Final Inspection12/13/200612/14/200612/13/2006 1:26:57 PMAPASS
Life safety finaled