ELE06-03549
| Electrical Rough-In | 12/13/2007 | 12/14/2007 | 12/14/2007 4:19:44 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 12/13/2007 at 6:30:33 PM. Contact: ###-####. met owner ok to cover kitchen and extension into already approved add-on area
|
ELE07-04127
| Electrical Rough-In | 12/14/2007 | 12/14/2007 | 12/14/2007 3:33:41 PM | P | PASS |
|
|
lynn Phone #: ###-#### called contractor, ric ok
|
ELE07-03612
| Electrical Rough-In | 12/13/2007 | 12/14/2007 | 12/14/2007 2:51:01 PM | P | PASS |
|
|
For ABOVE CEILING GRID INSPECTION - See Jerry - ###-#### Phone #: ###-#### Internet Inspection Request from: Tracy Robertson ok to cover dropped ceiling
|
ELE07-03958
| Electrical Rough-In | 12/14/2007 | 12/14/2007 | 12/14/2007 2:05:38 PM | P | PASS |
|
|
rocky Note: uifer Phone #: ###-#### called contractor, ok to pour concrete encased electrode
|
ELE07-03741
| Final | 12/14/2007 | 12/14/2007 | 12/14/2007 1:14:04 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 12/14/2007 at 9:58:03 AM. Contact: ###-####. corrections made, ok to final
|
ELE07-03789
| Final | 12/14/2007 | 12/14/2007 | 12/14/2007 12:28:36 PM | P | CANC |
|
|
Dale; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt wrong type request, see ri
|
ELE07-03789
| Electrical Rough-In | 12/14/2007 | 12/14/2007 | 12/14/2007 12:28:19 PM | P | PASS |
|
|
Dale; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt corrections made, called owner, ric ok garage, kitchen, family room
|
ELE07-04123
| Final | 12/13/2007 | 12/14/2007 | 12/14/2007 10:21:36 AM | A | PASS |
|
|
Call for access. Clay ###-####. Thanks. Phone #: ###-#### Internet Inspection Request from: Clay Morgan see ri comment for receptacle, ok to final
|
ELE07-04123
| Electrical Rough-In | 12/14/2007 | 12/14/2007 | 12/14/2007 10:00:21 AM | A | PASS |
|
|
Call for access. Clay ###-####. Thanks. Phone #: ###-#### Internet Inspection Request from: Clay Morgan ok to cover u/g, ric ok, told contractor to add receptacle to south wall of addition to meet 10'-20' rule
|
ELE07-03904
| Final | 12/13/2007 | 12/14/2007 | 12/14/2007 9:57:15 AM | A | PART |
|
|
jason Phone #: ###-#### looked at main bay only, said ok to move items in providing access still available for inspection, did not look at little office in main bay, still putting in lights and another door to be installed
|
ELE04-00180
| Electrical Rough-In | 12/10/2007 | 12/14/2007 | 12/14/2007 9:30:32 AM | A | FAIL |
|
|
John Please call 15 min before going out Phone #: ###-#### met owner, left correction notice, BCC all make-up shall be done, NEC 210.70(A)(2)(c) shall provide switch for lighting at top of stairs-to control from top or bottom (3-way), 314.17(C) shall staple nm cable within 8" of box
|
ELE07-03318
| Final | 12/13/2007 | 12/14/2007 | 12/14/2007 8:23:28 AM | A | PASS |
|
|
Final inspection. Please call Bobby Langner Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson ok to final, met contractor, signed occupancy card
|