FIR07-00977
| INSP-Sprinkler Rough-in | 12/14/2007 | 12/14/2007 | 12/17/2007 8:14:30 AM | P | PART |
|
|
OH rough-in at the hard lid soffits and ceilings is approved for cover.
|
FIR07-00983
| INSP-Final Inspection | 12/14/2007 | 12/14/2007 | 12/17/2007 8:13:15 AM | P | PASS |
|
|
Fire sprinkler demo permit finaled.
|
FIR07-00937
| INSP-Sprinkler Rough-in | 12/13/2007 | 12/14/2007 | 12/14/2007 3:15:09 PM | A | FAIL |
|
|
Noted significant changes regarding the actual installation v. approved plans (main and branchline changes, supply riser changes, added heads, relocated sw heads, etc.), noted missing heads at closets on the 2nd floor, missing heads under the stairs 1st floor, added heads in mech, closets, branchline changes at the design area, noted the UG supply has been installed and covered without an inspection and will not be accepted until conditions of approval are met.
|
FIR07-00877
| INSP-Final Inspection | 12/10/2007 | 12/14/2007 | 12/14/2007 2:39:24 PM | A | PART |
|
|
Still missing required hanger support at one location, remaining work accepted.
|
BLD07-02303
| FIRE-Final Inspection | 12/12/2007 | 12/14/2007 | 12/14/2007 1:34:05 PM | P | NR |
|
|
Not ready...KR
|
BLD07-01562
| FIRE-Final Inspection | 12/13/2007 | 12/14/2007 | 12/14/2007 1:32:20 PM | A | FAIL |
|
|
Missing two fire extinguishers, one for the office area 1st floor and one for the warehouse, need to repair one EM light at the main entry/exit.
|
FIR07-00328
| INSP-Final Inspection | 12/13/2007 | 12/14/2007 | 12/14/2007 1:29:59 PM | A | PASS |
|
|
Fire alarm permit finaled.
|
FIR07-00895
| INSP-Sprinkler Rough-in | 12/13/2007 | 12/14/2007 | 12/14/2007 10:56:50 AM | A | PART |
|
|
OH sprinker system modifications are approved for cover at the drop ceilings, noted one change at supply piping to a head in the hallway is acceptable, final pending ceiling tile and escutcheons.
|
FIR07-00983
| INSP-Sprinkler Rough-in | 12/13/2007 | 12/14/2007 | 12/14/2007 10:54:27 AM | A | PASS |
|
|
Scope of work completed as indicated, inspection passed.
|
FIR07-00913
| INSP-Sprinkler Rough-in/Hydro | 12/14/2007 | 12/14/2007 | 12/14/2007 10:22:40 AM | A | FAIL |
|
|
Inspection for cover denied where the two 4" mains pass through the floor without provision for seismic clearance-need to install flex couplings or provide req. clearance per NFPA 13. The three heads at the storefront hard lid ceilings are okay to cover.
|
FIR07-00327
| INSP-Final Inspection | 12/13/2007 | 12/14/2007 | 12/14/2007 10:19:18 AM | A | PASS |
|
|
Correction completed, fire alarm permit finaled.
|
FIR07-00662
| FIR-Aging Inspection | 12/14/2007 | 12/14/2007 | 12/14/2007 10:18:31 AM | | DEFR |
|
|
Under construction, work in progress.
|