FIR10-00144
| FIR-Aging Inspection | 12/14/2010 | 12/14/2010 | 12/15/2010 8:12:15 AM | | NR |
|
|
Work is in progress
|
FIR10-00615
| INSP-Final Inspection | 12/13/2010 | 12/14/2010 | 12/15/2010 7:53:30 AM | A | FAIL |
|
|
The sprinkler piping can be covered but this permit can not be finaled until the draftstop that is causing an obstruction to the upright sprinkler coverage has been removed as discussed.
|
FIR10-00500
| INSP-Sprinkler Rough-in | 12/14/2010 | 12/14/2010 | 12/15/2010 7:51:25 AM | P | PASS |
|
|
The sprinkler piping located above the hardlids in the restroom areas can be covered.
|
FIR39-00017
| FIR-Aging Inspection | 12/14/2010 | 12/14/2010 | 12/14/2010 2:30:26 PM | | FAIL |
|
|
I can't believe this guy still has a license.
|
FIR39-00016
| FIR-Aging Inspection | 12/14/2010 | 12/14/2010 | 12/14/2010 2:28:37 PM | | CANC |
|
|
Crazy guy lives here.
|
FIR10-00626
| INSP-Sprinkler Rough-in | 12/13/2010 | 12/14/2010 | 12/14/2010 2:26:35 PM | A | PASS |
|
|
Rough-in passed. Sprinkler piping can be covered.
|
FIR10-00523
| INSP-Final Inspection | 12/14/2010 | 12/14/2010 | 12/14/2010 2:23:35 PM | P | CANC |
|
|
To be rescheduled for tomorrow morning.
|
BLD10-00987
| FIRE-Final Inspection | 12/13/2010 | 12/14/2010 | 12/14/2010 10:35:48 AM | A | FAIL |
|
|
No life safety was performed due to the project related fire alarm and fire sprinkler permits not being ready for inspection.
|
FIR10-00470
| INSP-Final Inspection | 12/13/2010 | 12/14/2010 | 12/14/2010 10:34:53 AM | A | FAIL |
|
|
The forward flush passed inspection. Items remaining for a temporary occupancy in the service portion, include the testing of the fire alarm panel interconnection.
|
FIR10-00523
| INSP-Final Inspection | 12/13/2010 | 12/14/2010 | 12/14/2010 10:30:23 AM | A | FAIL |
|
|
The fire alarm panel is using the same phone lines for both phone line 1 and phone line 2 outputs. Tried to test the flow switch and it exceed the maximum 90 second for alarm. Testing was stopped and will need to be rescheduled. Also the remote annunciator needs to be permanantly mounted or signage provided as discussed to direct the responding fire dept personnel to the FACP location in the second floor storage room.
|