Inspections for the day of: Tuesday, December 14, 2010.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR10-00144 FIR-Aging Inspection12/14/201012/14/201012/15/2010 8:12:15 AM NR
Work is in progress
FIR10-00615 INSP-Final Inspection12/13/201012/14/201012/15/2010 7:53:30 AMAFAIL
The sprinkler piping can be covered but this permit can not be finaled until the draftstop that is causing an obstruction to the upright sprinkler coverage has been removed as discussed.
FIR10-00500 INSP-Sprinkler Rough-in12/14/201012/14/201012/15/2010 7:51:25 AMPPASS
The sprinkler piping located above the hardlids in the restroom areas can be covered.
FIR39-00017 FIR-Aging Inspection12/14/201012/14/201012/14/2010 2:30:26 PM FAIL
I can't believe this guy still has a license.
FIR39-00016 FIR-Aging Inspection12/14/201012/14/201012/14/2010 2:28:37 PM CANC
Crazy guy lives here.
FIR10-00626 INSP-Sprinkler Rough-in12/13/201012/14/201012/14/2010 2:26:35 PMAPASS
Rough-in passed. Sprinkler piping can be covered.
FIR10-00523 INSP-Final Inspection12/14/201012/14/201012/14/2010 2:23:35 PMPCANC
To be rescheduled for tomorrow morning.
BLD10-00987 FIRE-Final Inspection12/13/201012/14/201012/14/2010 10:35:48 AMAFAIL
No life safety was performed due to the project related fire alarm and fire sprinkler permits not being ready for inspection.
FIR10-00470 INSP-Final Inspection12/13/201012/14/201012/14/2010 10:34:53 AMAFAIL
The forward flush passed inspection. Items remaining for a temporary occupancy in the service portion, include the testing of the fire alarm panel interconnection.
FIR10-00523 INSP-Final Inspection12/13/201012/14/201012/14/2010 10:30:23 AMAFAIL
The fire alarm panel is using the same phone lines for both phone line 1 and phone line 2 outputs. Tried to test the flow switch and it exceed the maximum 90 second for alarm. Testing was stopped and will need to be rescheduled. Also the remote annunciator needs to be permanantly mounted or signage provided as discussed to direct the responding fire dept personnel to the FACP location in the second floor storage room.