Inspections for the day of: Wednesday, December 14, 2011.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD11-01901 FIRE-Conference12/14/201112/14/201112/14/2011 3:47:06 PMPDONE
On site conference regarding fire code review notes, life safety items, fire alarm permit application for new tamper switch monitoring at the control vavles for the fire protection DCVA, etc.
FIR11-00571 INSP-Final Inspection12/13/201112/14/201112/14/2011 3:24:34 PMPNR
Charles is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus
FIR11-00571 INSP-Sprinkler Rough-in12/14/201112/14/201112/14/2011 3:24:02 PMAFAIL
Noted items include #3, 5 and 7 on the fire code review comments regarding seismic brace attatchments to Z purlins, trapeeze calculations, and supervised tamper control vavles at the new DCVA. Also noted missing lateral branch line restraints per NFPA 13 2010 9.3.6.4 and plan detail. The compressor room appears inadequately heated.
FIR11-00571 INSP-Sprinkler Rough-in/Hydro12/13/201112/14/201112/14/2011 3:08:20 PMPPART
Overhead hydrostatic test passed after temp. bypass of the PRV.
FIR11-00534 INSP-Sprinkler Rough-in12/14/201112/14/201112/14/2011 3:02:40 PMAPART
BLD11-02801 FIRE-Sprinkler Rough-in12/14/201112/14/201112/14/2011 3:01:59 PMAPART
Overhead fire sprinkler work and noted correction items passed rough-in inspection.