Inspections for the day of: Wednesday, December 14, 2016.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTom Saunders
TitleELE-INSPECTOR
Phone #208-794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-03127 Final12/14/201612/14/201612/14/2016 2:45:00 PMPFAIL
Phone #: ###-#### Inspection requested via web by Dan Rohl....

1. countertop in dining room needs outlets so that no point along the wall line is more than 24" to outlet 210.52(C)

2. microwave circuit and dishwasher need breaker lock outs installed
ELE16-03566 Electrical Rough-In12/14/201612/14/201612/14/2016 2:17:53 PMPPASS
ceiling grid; rob Phone #: ###-####....

ok to cover...only area still needing inspection is warehouse/garage area
ELE16-03471 Temporary Service12/14/201612/14/201612/14/2016 1:31:32 PMPPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn....

t/s u/g n ok
ELE16-03470 Temporary Service12/14/201612/14/201612/14/2016 1:31:03 PMPPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn...

t/s u/g n ok
ELE16-03472 Temporary Service12/14/201612/14/201612/14/2016 1:30:35 PMPPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn...

t/s u/g n ok
ELE16-03473 Temporary Service12/14/201612/14/201612/14/2016 1:30:01 PMPPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn...

t/s u/g n ok
ELE16-01961 Electrical Rough-In12/14/201612/14/201612/14/2016 12:55:52 PMPPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton...

wallcover mechanical room as marked on plan
ELE16-03057 Final12/13/201612/14/201612/14/2016 12:19:17 PMPPART
Temporary final Phone #: ###-#### Inspection requested via web by Tom Jenkins...

90 percent complete....left to check
front desk reception counter outlets
LV openings
procedure lights
work station cutin outlets
cut in in physical therapy
check exit signs
lockout on dishwasher
ELE16-00910 Final12/14/201612/14/201612/14/2016 11:30:39 AMPNR
Mark Phone #: ###-####...

discussed with homeowner what needed done before final inspection
ELE16-02407 Final12/13/201612/14/201612/14/2016 10:52:28 AMAFAIL
Phone #: ###-#### Inspection requested via web by Rhonda Yoast....

1. overcurrent protection of a/c unit is too large
2. micro circuit needs breaker lockout installed
3. sump pump needs GFI protection
4. outlet in downstairs bath needs outlet plate
5. master closet light has less than 12" of clearance from edge of shelf
6. bath outlets have no power...GFI will not set
ELE16-03026 Final12/14/201612/14/201612/14/2016 9:44:29 AMAPASS
Phone #: ###-#### Inspection requested via web by Emmet Bushman....

ok to final
ELE16-04023 Permanent Service12/13/201612/14/201612/14/2016 8:59:52 AMAFAIL
There hasn''t been power for over a year, the access code is 3244, the lock box is on the railing on the front porch, any questions please let me know at ###-####, thx, TW Phone #: ###-#### Inspection requested via web by Stephen Kren...

grounding shall be brought up to code..2 ground rods

open spaces in panel cover shall be sealed...breaker blank