Inspections for the day of: Thursday, December 14, 2017.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-01337 Electrical Rough-In12/13/201712/14/201712/14/2017 1:40:21 PMPPASS
We are requesting a rough-in inspection for 2nd floor walls and ceilings and 1st floor complete ceiling for tomorrow afternoon. Our contact is Rick @ ###-####. Thank you,
Phone #: ###-#### Inspection requested via web by Clint Tate
219 thru 234 and 238, level 1 firelids except west meeting room rough in ok cover
ELE17-04204 Electrical Rough-In12/14/201712/14/201712/14/2017 12:47:50 PMPPASS
Ben Phone #: ###-####
Small wall to west of elevators rough in ok cover
ELE17-03734 Electrical Rough-In12/13/201712/14/201712/14/2017 11:39:56 AMAPART
This inspection is for temporary occupancy of the partial prep room which failed the last inspection due to the BLD permit still under review. Our understanding is this would be resolved between the Architect and City today. Site Contact: Luke Hardy, ###-####. Phone #: ###-#### Inspection requested via web by Larry Looney
No rough in needed. Created to note for ok occupy prep room A.
ELE17-04192 Electrical Rough-In12/13/201712/14/201712/14/2017 10:41:07 AMAPASS
Phone #: ###-#### Inspection requested via web by Ryan Wilson
Under ground not in at time of inspection, Will create P/S, contractor to provide minimum clearance above garage roof as per 230.24. Swing may cross over peak of roof, may be issue. House and garage rough in ok cover
ELE17-04192 Permanent Service12/14/201712/14/201712/14/2017 10:40:48 AMPPASS
Phone #: ###-#### Inspection requested via web by Ryan Wilson
Shall provide clearance for overhead service entrance conductors as per 230.24. May cross garage roof peak may be issue called contractor to inform.
p/s o/h n ok
ELE17-04203 Electrical Rough-In12/13/201712/14/201712/14/2017 10:12:45 AMAFAIL
Call Chase if needed - ###-####. Basement rough-in only Phone #: ###-#### Inspection requested via web by Cyndi Dale
300.15- All wiring shall terminate in a box. Open wiring out of flex, MC in soffit area. All covers shall be accessible after installation.
314.25- All boxes shall have covers installed. Several boxes with wiring hanging out in soffit area.
330.12- MC shall not be installed where subject to damage. MC hanging below soffit and below soffit framing member.
ELE17-03103 Final12/14/201712/14/201712/14/2017 8:33:18 AMAPASS
Garage code is 9045 Phone #: ###-#### Inspection requested via web by Kevin Heideman Final ok