Inspections for the day of: Thursday, December 14, 2017.
Number of inspections: 20
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR17-00445 INSP-Sprinkler Rough-in12/14/201712/14/201712/14/2017 2:09:48 PMPPASS
Rough to cover inspection for underground supply complete, approved for cover.
FIR17-00459 INSP-Sprinkler Rough-in12/14/201712/14/201712/14/2017 2:07:03 PMPPASS
Rough to cover inspection for underground supply complete, approved for cover.
FIR17-00461 INSP-Sprinkler Rough-in12/14/201712/14/201712/14/2017 2:06:50 PMPPASS
Rough to cover inspection for underground supply complete, approved for cover.
FIR17-00458 INSP-Sprinkler Rough-in12/14/201712/14/201712/14/2017 2:06:36 PMPPASS
Rough to cover inspection for underground supply complete, approved for cover.
FIR17-00452 INSP-Sprinkler Rough-in12/14/201712/14/201712/14/2017 2:06:22 PMPPASS
Rough to cover inspection for underground supply complete, approved for cover.
FIR17-00449 INSP-Sprinkler Rough-in12/14/201712/14/201712/14/2017 2:05:22 PMPPASS
Rough to cover inspection for underground supply complete, approved for cover.
BLD17-01581 FIRE-Final Inspection12/13/201712/14/201712/14/2017 1:30:17 PMPPART
Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguishers are in place with current inspection tags, knox box is located by front entry, fuel system inspection complete by fire department. Partial final inspection complete for life fire safey, door hardware for rear sliding glass door needs to be changed to be code compliant, 30 day TCO approved for life fire safety per conversation with Scott Arellano.
FIR17-00727 INSP-Final Inspection12/14/201712/14/201712/14/2017 1:10:42 PMPPASS
Final fire alarm inspection complete, as-builds will be submitted for modifications that were made to system.
FIR17-00435 INSP-Final Inspection12/14/201712/14/201712/14/2017 1:08:24 PMPPASS
Final fire sprinkler inspection complete.
BLD15-02939 FIRE-Final Inspection12/14/201712/14/201712/14/2017 12:29:42 PMPPASS
No fire sprinklers, no fire alarms, fire extinguisher is mounted with a current inspection tag. Final life fire safety inspection complete.
BLD17-01238 FIRE-Conference12/13/201712/14/201712/14/2017 12:16:26 PMAFAIL
Path of egress is more than what was shown on the proposed TCO plan submitted to Jason Blais, coolers are being used so corridor from coolers to stairs is to be included for egress purposes, fire sprinklers will need to be added to basement corridor before TCO can be approved for life fire safety. Sheetrock will need to be installed on corridor wall to seperate area still under construction (area of seperation is where the fire sprinkler system is impaired) from the noted path of egress before TCO can be approved for life fire safety. A fire watch will be required for area's where the fire sprinkler system has been impaired while building is occupied or active fire sprinkler protection will need to be put in the area where the sprinkler piping was removed before TCO can be approved for life fire safety. TCO required items have been discussed with Scott Arellano and Ron Johnson and they are in aggreement for the items mentioned to be completed before TCO can be approved for requested areas.
FIR17-00682 INSP-Sprinkler Rough-in12/13/201712/14/201712/14/2017 12:03:51 PMAPART
Fire sprinkler work for food prep area complete (part of the TCO requested area) Fire sprinklers will need to be added to the area for the path of egress, issue has been discussed with job superintendant.
FIR17-00729 INSP-Sprinkler Rough-in12/14/201712/14/201712/14/2017 11:45:31 AMPPASS
Rough to cover inspection for underground supply complete, approved for cover.
FIR17-00501 INSP-Final Inspection12/14/201712/14/201712/14/2017 11:43:03 AMPPASS
Final inspection for underground supply complete.
FIR17-00206 INSP-Sprinkler Rough-in12/13/201712/14/201712/14/2017 11:41:51 AMAPART
Rough to cover inspection for overhead fire sprinkler piping on level 4 (Top level) complete, approved for cover.
FIR17-00726 INSP-Sprinkler Rough-in12/13/201712/14/201712/14/2017 10:32:16 AMAPASS
Rough to cover inspection for underground, remote FDC and remote main drain complete, approved for cover.
BLD16-02409 FIRE-Final Inspection12/13/201712/14/201712/14/2017 10:17:25 AMAPASS
Fire sprinkler inspection complete, fire alarm inspection complete. Final life fire safety complete.
FIR17-00653 INSP-Final Inspection12/14/201712/14/201712/14/2017 10:00:59 AMAPASS
Final fire alarm inspection complete
FIR16-00794 INSP-Final Inspection12/13/201712/14/201712/14/2017 9:59:50 AMAPASS
Final fire sprinkler inspection complete.
FIR17-00505 INSP-Final Inspection12/13/201712/14/201712/13/2017 10:02:25 AMACANC
Please call Jake before heading out, thank you! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello