Inspections for the day of: Thursday, December 15, 2005.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00715 INSP-Final Inspection12/15/200512/15/200512/15/2005 5:57:04 PMPPART
All issues are satisfactory, final pending the related TI alarm permit final.
FIR05-00169 INSP-Final Inspection12/14/200512/15/200512/15/2005 5:49:16 PMPFAIL
Vent tube at duct detector 1st floor is incorrect, smoke detector at the electrical room 2nd floor is too close to the wall, 2nd and 3rd floor strobe in the common corridor is too low, pull station at the north roof is not functional, horn in the mech. penthouse is not operational, need to update map reflecting actual location of the floor control valves for the sprinkler system, not a complete inspection at this time, need to repair defficiencies and call for reinspect.
FIR05-00735 INSP-Final Inspection12/14/200512/15/200512/15/2005 5:41:14 PMPFAIL
The lens on wall mounted strobes at each device in the TI area are mounted too low, not meeting min. code requirements.
FIR05-00734 INSP-Final Inspection12/14/200512/15/200512/15/2005 5:39:45 PMPFAIL
The lens on wall mounted strobes at each device in the TI area are mounted too low, not meeting min. code requirements.
FIR05-00385 INSP-Final Inspection12/15/200512/15/200512/15/2005 5:34:29 PMPPASS
c/n items are complete, fire sprinkler permit finaled.
FIR04-00812 INSP-Final Inspection12/15/200512/15/200512/15/2005 5:33:11 PMPPASS
Underground fire supply line finaled.
BLD05-03075 FIRE-Conference12/15/200512/15/200512/15/2005 4:47:08 PMPDONE
Discussion regarding project related fire alarm and sprinkler requirements and general life safety items as referenced on plan review notes.
BLD05-02816 FIRE-Conference12/15/200512/15/200512/15/2005 4:45:07 PMPDONE
Discussion regarding project associated fire alarm and sprinkler permit requirements and general life safety items as referenced on plan review notes.
FIR05-00715 INSP-Final Inspection12/14/200512/15/200512/15/2005 10:52:13 AMADEFR
Inspection to be performed this afternoon after 2:00 as discussed and agreed previously.
BLD05-01910 FIRE-Final Inspection12/14/200512/15/200512/15/2005 10:21:11 AMAPASS
Fire life safety passed inspection, c/n items have been completed as required.
BLD04-01822 FIRE-Final Inspection12/14/200512/15/200512/15/2005 10:16:10 AMAPASS
c/n items have been completed, inspection passed.
MIS05-00229 FIR-Final12/14/200512/15/200512/15/2005 9:31:48 AMAFAIL
Need to mount the provided fire extinguishers on the wall along a normal path of travel with the handle no higher than 48" AFF, provide signage above the office main entry/exit door.