FIR05-00493
| INSP-Final Inspection | 12/14/2005 | 12/15/2005 | 12/15/2005 4:36:09 PM | P | CANC |
|
|
Jonathan is the contact @ ###-####. Thanks; Phone #: ###-#### Internet Inspection Request from: Trent Bice
|
BLD05-01564
| FIRE-Final Inspection | 12/15/2005 | 12/15/2005 | 12/15/2005 3:51:36 PM | P | PART |
|
|
A temporary occupancy was given with Dave Hannimen's permission until the fire alarm permit is finaled. The exit sign on the second floor at the top of the west stairs needs repaired and the emergency light on the first floor east exit needs repaired.
|
FIR05-00558
| INSP-Final Inspection | 12/15/2005 | 12/15/2005 | 12/15/2005 3:42:05 PM | P | FAIL |
|
|
Wrong sample tube has been installed on the duct smoke detector. There is a distortion/buzz over the voice circuit that needs addressed. New strobes need to be sync'd with the old.
|
FIR05-00798
| INSP-Final Inspection | 12/15/2005 | 12/15/2005 | 12/15/2005 3:40:34 PM | P | FAIL |
|
|
Inspection was only for rough-in. Sprinkler piping is ok to cover. Need to install ceiling tile at sprinkler pendants.
|