FIR08-00605
| INSP-Sprinkler Rough-in/Hydro | 12/12/2008 | 12/15/2008 | 12/15/2008 5:18:48 PM | P | FAIL |
|
|
See stamped plan set for annotations regarding corrections including missing coverage at two closets, min. spacing exceeded at one location, one head too close to a heat vent, missing head at a branchline, walls at the pool room #3 may create overspacing to adjacent heads, noted possible light fixture obstructions due to some heads in close proximity to junction boxes, branchline above the pool will require special consideration for cold cavity protection as installed, also noted significant field modifications at some areas in pipe sizes and branchline routing which differ from approved plans and will require resubmittal. Noted UG supply line flush has not yet been performed and inspectors test/drain not complete. See plan review notes items #17,24,28,31,32, and 49 for details pertaining to today's comments. NOTE: Riser room and the west half of the 1st floor only inspected today- installation is not approved for cover at this time.
|
FIR08-00574
| INSP-Final Inspection | 12/14/2008 | 12/15/2008 | 12/15/2008 4:46:32 PM | P | DEFR |
|
|
Scheduled by a contractor via Hello! on 12/14/2008 at 10:31:12 PM. Contact: ###-####.
|
BLD08-02125
| FIRE-Final Inspection | 12/15/2008 | 12/15/2008 | 12/15/2008 4:46:17 PM | A | NR |
|
|
Scheduled 12/16
|
FIR08-00811
| INSP-Final Inspection | 12/15/2008 | 12/15/2008 | 12/15/2008 2:25:03 PM | P | PASS |
|
|
Fire sprinkler permit work finaled.
|
FIR08-00777
| INSP-Final Inspection | 12/15/2008 | 12/15/2008 | 12/15/2008 2:24:30 PM | P | PASS |
|
|
Fire sprinkler permit okay for final.
|
BLD08-00571
| FIRE-Conference | 12/15/2008 | 12/15/2008 | 12/15/2008 11:41:25 AM | A | DONE |
|
|
Project related fire alarm permit site inspection and approval to be finished prior to building life safety.
|
FIR06-00351
| INSP-Conference | 12/13/2008 | 12/15/2008 | 12/15/2008 11:38:07 AM | A | DONE |
|
|
Regarding portions of permit work both complete and incompleted to date.
|
FIR08-00817
| INSP-Final Inspection | 12/12/2008 | 12/15/2008 | 12/15/2008 11:34:17 AM | A | PASS |
|
|
OH rough-in and final inspections completed in the same visit, scope of fire sprinkler permit work finaled.
|