Inspections for the day of: Monday, December 15, 2008.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00605 INSP-Sprinkler Rough-in/Hydro12/12/200812/15/200812/15/2008 5:18:48 PMPFAIL
See stamped plan set for annotations regarding corrections including missing coverage at two closets, min. spacing exceeded at one location, one head too close to a heat vent, missing head at a branchline, walls at the pool room #3 may create overspacing to adjacent heads, noted possible light fixture obstructions due to some heads in close proximity to junction boxes, branchline above the pool will require special consideration for cold cavity protection as installed, also noted significant field modifications at some areas in pipe sizes and branchline routing which differ from approved plans and will require resubmittal. Noted UG supply line flush has not yet been performed and inspectors test/drain not complete. See plan review notes items #17,24,28,31,32, and 49 for details pertaining to today's comments. NOTE: Riser room and the west half of the 1st floor only inspected today- installation is not approved for cover at this time.
FIR08-00574 INSP-Final Inspection12/14/200812/15/200812/15/2008 4:46:32 PMPDEFR
Scheduled by a contractor via Hello! on 12/14/2008 at 10:31:12 PM. Contact: ###-####.
BLD08-02125 FIRE-Final Inspection12/15/200812/15/200812/15/2008 4:46:17 PMANR
Scheduled 12/16
FIR08-00811 INSP-Final Inspection12/15/200812/15/200812/15/2008 2:25:03 PMPPASS
Fire sprinkler permit work finaled.
FIR08-00777 INSP-Final Inspection12/15/200812/15/200812/15/2008 2:24:30 PMPPASS
Fire sprinkler permit okay for final.
BLD08-00571 FIRE-Conference12/15/200812/15/200812/15/2008 11:41:25 AMADONE
Project related fire alarm permit site inspection and approval to be finished prior to building life safety.
FIR06-00351 INSP-Conference12/13/200812/15/200812/15/2008 11:38:07 AMADONE
Regarding portions of permit work both complete and incompleted to date.
FIR08-00817 INSP-Final Inspection12/12/200812/15/200812/15/2008 11:34:17 AMAPASS
OH rough-in and final inspections completed in the same visit, scope of fire sprinkler permit work finaled.