BLD09-00267
| FIRE-Final Inspection | 12/15/2009 | 12/15/2009 | 12/15/2009 3:34:23 PM | P | CANC |
|
|
I had a conference with the building contractor about needing the data sheet for the fire proofing applied in the dog house area and also not all of the wood has been covered in the dog house area. No othe life safety items have been inspected.
|
FIR09-00291
| INSP-Final Inspection | 12/14/2009 | 12/15/2009 | 12/15/2009 3:19:18 PM | A | PASS |
|
|
Permit finaled. Forward flush passed.
|
FIR09-00507
| INSP-Alarm Testing | 12/14/2009 | 12/15/2009 | 12/15/2009 1:20:14 PM | A | FAIL |
|
|
fire alarm panel interconnects to NAC panels all tested OK. Interconnections with fire sprinkler devices tested OK. Corrections needed. Refer to on site city approved drawings. Corrections needed include (but are not limited to) overspaced notification devices, missing notificaion, device placement and type not matching plans, smoke detectors for door release mounted incorrectly, smoke above panel is incorrectly placed, however contractor stated will delete rather than move. Ralph to fax signal report for verification.
|