Inspections for the day of: Tuesday, December 15, 2009.
Number of inspections: 3
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD09-00267 FIRE-Final Inspection12/15/200912/15/200912/15/2009 3:34:23 PMPCANC
I had a conference with the building contractor about needing the data sheet for the fire proofing applied in the dog house area and also not all of the wood has been covered in the dog house area. No othe life safety items have been inspected.
FIR09-00291 INSP-Final Inspection12/14/200912/15/200912/15/2009 3:19:18 PMAPASS
Permit finaled. Forward flush passed.
FIR09-00507 INSP-Alarm Testing12/14/200912/15/200912/15/2009 1:20:14 PMAFAIL
fire alarm panel interconnects to NAC panels all tested OK. Interconnections with fire sprinkler devices tested OK. Corrections needed. Refer to on site city approved drawings. Corrections needed include (but are not limited to) overspaced notification devices, missing notificaion, device placement and type not matching plans, smoke detectors for door release mounted incorrectly, smoke above panel is incorrectly placed, however contractor stated will delete rather than move. Ralph to fax signal report for verification.