ELE14-03431
| Final | 12/12/2014 | 12/15/2014 | 12/15/2014 2:29:56 PM | P | PASS |
|
|
added can lights and a couple outlets Phone #: ###-#### Inspection requested via web by Randy Fletcher Final OK
|
ELE14-02937
| Final | 12/15/2014 | 12/15/2014 | 12/15/2014 2:00:51 PM | P | PASS |
|
|
As late as possible Phone #: 2088671666 >> Inspection requested via mobile web by Melinda Corrections made, Final OK
|
ELE14-03355
| Electrical Rough-In | 12/14/2014 | 12/15/2014 | 12/15/2014 1:28:23 PM | P | PASS |
|
|
Soffit inspection. Contact Ryan Wake Phone #: ###-#### Inspection requested via web by Chris Chesnut Soffit inspection only, Cans on home have fire boxes on them, Soffits ok to cover
|
ELE11-02581
| Final | 12/12/2014 | 12/15/2014 | 12/15/2014 1:04:53 PM | P | PASS |
|
|
Jody Phone #: ###-#### Final OK
|
ELE12-01787
| ELE-Aging Inspection | 12/15/2014 | 12/15/2014 | 12/15/2014 11:53:40 AM | | DONE |
|
|
Left message for Shaun
|
ELE11-02529
| ELE-Aging Inspection | 12/15/2014 | 12/15/2014 | 12/15/2014 11:51:17 AM | | DONE |
|
|
Spoke to David, still under construction, but close to finished.
|
ELE13-00343
| ELE-Aging Inspection | 12/15/2014 | 12/15/2014 | 12/15/2014 11:47:33 AM | | DONE |
|
|
Spoke to Steve, he will look into project.
|
ELE14-03429
| Permanent Service | 12/12/2014 | 12/15/2014 | 12/15/2014 10:57:40 AM | A | FAIL |
|
|
Call Eric with questions. Lock box on back door #8791 Phone #: ###-#### Inspection requested via web by Eric Schroeder 250.53 Supplemental ground required Subpanel lugs are not rated for two conductors 250.24 Grounded conductor shall not be connected to non current carrying metal parts, grounded and grounding condutors shall be isolated from each other at subpanels Subpanel does not have a grounded conductor, yet grounded conductors are in use on line side,
|
ELE14-03392
| Permanent Service | 12/14/2014 | 12/15/2014 | 12/15/2014 9:56:56 AM | A | PASS |
|
|
Need a permanant service so Idaho power can install a meter Phone #: ###-#### Inspection requested via web by John Edwards PS, UG, N, OK
|
ELE14-03392
| Rough-In Permanent Service | 12/15/2014 | 12/15/2014 | 12/15/2014 9:56:36 AM | P | FAIL |
|
|
Need a permanant service so Idaho power can install a meter Phone #: ###-#### Inspection requested via web by John Edwards 110.243 Service gear shall be legibly marked with available fault current, and date of calculation Meter needs address posted
|
ELE14-02927
| Final | 12/12/2014 | 12/15/2014 | 12/15/2014 9:16:34 AM | A | PASS |
|
|
final inspection, will be open if not please call , ###-#### Phone #: ###-#### Inspection requested via web by Rowdy Monroe final OK
|
ELE14-02937
| Final | 12/13/2014 | 12/15/2014 | 12/15/2014 8:49:25 AM | A | FAIL |
|
|
Phone #: 2088671666 >> Inspection requested via mobile web by Melinda spoke to owner, extension rings required where boxes are recessed in tile, nameplate for oven requires 40 amp breaker and needs disconnect means or lockout
|