Inspections for the day of: Monday, December 15, 2014.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorCevyn Recla
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE14-03431 Final12/12/201412/15/201412/15/2014 2:29:56 PMPPASS
added can lights and a couple outlets Phone #: ###-#### Inspection requested via web by Randy Fletcher
Final OK
ELE14-02937 Final12/15/201412/15/201412/15/2014 2:00:51 PMPPASS
As late as possible Phone #: 2088671666 >> Inspection requested via mobile web by Melinda
Corrections made, Final OK
ELE14-03355 Electrical Rough-In12/14/201412/15/201412/15/2014 1:28:23 PMPPASS
Soffit inspection. Contact Ryan Wake Phone #: ###-#### Inspection requested via web by Chris Chesnut
Soffit inspection only, Cans on home have fire boxes on them, Soffits ok to cover
ELE11-02581 Final12/12/201412/15/201412/15/2014 1:04:53 PMPPASS
Jody Phone #: ###-####
Final OK
ELE12-01787 ELE-Aging Inspection12/15/201412/15/201412/15/2014 11:53:40 AM DONE
Left message for Shaun
ELE11-02529 ELE-Aging Inspection12/15/201412/15/201412/15/2014 11:51:17 AM DONE
Spoke to David, still under construction, but close to finished.
ELE13-00343 ELE-Aging Inspection12/15/201412/15/201412/15/2014 11:47:33 AM DONE
Spoke to Steve, he will look into project.
ELE14-03429 Permanent Service12/12/201412/15/201412/15/2014 10:57:40 AMAFAIL
Call Eric with questions. Lock box on back door #8791 Phone #: ###-#### Inspection requested via web by Eric Schroeder
250.53 Supplemental ground required
Subpanel lugs are not rated for two conductors
250.24 Grounded conductor shall not be connected to non current carrying metal parts, grounded and grounding condutors shall be isolated from each other at subpanels
Subpanel does not have a grounded conductor, yet grounded conductors are in use on line side,
ELE14-03392 Permanent Service12/14/201412/15/201412/15/2014 9:56:56 AMAPASS
Need a permanant service so Idaho power can install a meter Phone #: ###-#### Inspection requested via web by John Edwards
PS, UG, N, OK
ELE14-03392 Rough-In Permanent Service12/15/201412/15/201412/15/2014 9:56:36 AMPFAIL
Need a permanant service so Idaho power can install a meter Phone #: ###-#### Inspection requested via web by John Edwards
110.243 Service gear shall be legibly marked with available fault current, and date of calculation
Meter needs address posted
ELE14-02927 Final12/12/201412/15/201412/15/2014 9:16:34 AMAPASS
final inspection, will be open if not please call , ###-#### Phone #: ###-#### Inspection requested via web by Rowdy Monroe
final OK
ELE14-02937 Final12/13/201412/15/201412/15/2014 8:49:25 AMAFAIL
Phone #: 2088671666 >> Inspection requested via mobile web by Melinda
spoke to owner,
extension rings required where boxes are recessed in tile,
nameplate for oven requires 40 amp breaker and needs disconnect means or lockout