BLD15-04350
| FIRE-Final Inspection | 12/15/2015 | 12/15/2015 | 12/15/2015 3:27:44 PM | P | FAIL |
|
|
All exterior doors in the warehouse have thumb turn deadbolts, need to be single action door hardware. Exit signs in building are not self-illuminated exit signs with emergency power source, exit signs need to be changed to self-illuminated with emergency power source.
|
BLD15-01216
| FIRE-Final Inspection | 12/15/2015 | 12/15/2015 | 12/15/2015 2:43:15 PM | P | PASS |
|
|
No fire sprinkler modifications, no fire alarms, previously noted items repaired, ADA compliant hardware installed on one of the pocket doors, hardware for the other two pockets doors on back order, will be installed when received, exit signs repaired and in working order, paddle type door handle installed on restroom door, fire extinguisher mounted and tagged. Life fire safety inspection passed/complete.
|
BLD15-04096
| FIRE-Final Inspection | 12/15/2015 | 12/15/2015 | 12/15/2015 2:11:29 PM | P | PASS |
|
|
Previously noted items addressed, exit signs installed at the east and west exterior exit doors, panic door hardware installed on east side exit, thumb turn deadblot on west door changed to a double key type, door to remain unlocked sticker installed on doors exiting the designated tenant space. The remaining doors in the tenant space are round knob type, not paddle type, I did inform the tenant that this could be an issue for the final building inspection. Life fire safety inspection passed/complete.
|
FIR15-00661
| INSP-Sprinkler Rough-in/Hydro | 12/14/2015 | 12/15/2015 | 12/15/2015 11:15:11 AM | A | PASS |
|
|
200 psi for 2 hours hydrostatic test passed/complete for the 1st and 2nd floor wet systems.
|
FIR15-00736
| INSP-Sprinkler Rough-in | 12/15/2015 | 12/15/2015 | 12/15/2015 10:50:03 AM | P | PART |
|
|
Rough to cover inspection for the hard lids complete, approved for cover. Stairs will be added at a later date with heads installed under the stairs, contractor will call for inspection when complete.
|
BLD15-04359
| FIRE-Final Inspection | 12/14/2015 | 12/15/2015 | 12/15/2015 10:08:05 AM | A | PASS |
|
|
No fire sprinklers, no fire alarms. Life fire safety inspection passed/complete
|
FIR15-00821
| INSP-Sprinkler Rough-in/Hydro | 12/14/2015 | 12/15/2015 | 12/15/2015 9:35:09 AM | A | PASS |
|
|
Rough to cover inspection passed/complete, all area's approved for cover.
|
FIR15-00834
| INSP-Sprinkler Rough-in | 12/14/2015 | 12/15/2015 | 12/15/2015 8:39:30 AM | A | PASS |
|
|
Rough to cover inspection complete, approved for cover
|