Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD15-04350 FIRE-Final Inspection12/15/201512/15/201512/15/2015 3:27:44 PMPFAIL
All exterior doors in the warehouse have thumb turn deadbolts, need to be single action door hardware. Exit signs in building are not self-illuminated exit signs with emergency power source, exit signs need to be changed to self-illuminated with emergency power source.
BLD15-01216 FIRE-Final Inspection12/15/201512/15/201512/15/2015 2:43:15 PMPPASS
No fire sprinkler modifications, no fire alarms, previously noted items repaired, ADA compliant hardware installed on one of the pocket doors, hardware for the other two pockets doors on back order, will be installed when received, exit signs repaired and in working order, paddle type door handle installed on restroom door, fire extinguisher mounted and tagged. Life fire safety inspection passed/complete.
BLD15-04096 FIRE-Final Inspection12/15/201512/15/201512/15/2015 2:11:29 PMPPASS
Previously noted items addressed, exit signs installed at the east and west exterior exit doors, panic door hardware installed on east side exit, thumb turn deadblot on west door changed to a double key type, door to remain unlocked sticker installed on doors exiting the designated tenant space. The remaining doors in the tenant space are round knob type, not paddle type, I did inform the tenant that this could be an issue for the final building inspection. Life fire safety inspection passed/complete.
FIR15-00661 INSP-Sprinkler Rough-in/Hydro12/14/201512/15/201512/15/2015 11:15:11 AMAPASS
200 psi for 2 hours hydrostatic test passed/complete for the 1st and 2nd floor wet systems.
FIR15-00736 INSP-Sprinkler Rough-in12/15/201512/15/201512/15/2015 10:50:03 AMPPART
Rough to cover inspection for the hard lids complete, approved for cover. Stairs will be added at a later date with heads installed under the stairs, contractor will call for inspection when complete.
BLD15-04359 FIRE-Final Inspection12/14/201512/15/201512/15/2015 10:08:05 AMAPASS
No fire sprinklers, no fire alarms. Life fire safety inspection passed/complete
FIR15-00821 INSP-Sprinkler Rough-in/Hydro12/14/201512/15/201512/15/2015 9:35:09 AMAPASS
Rough to cover inspection passed/complete, all area's approved for cover.
FIR15-00834 INSP-Sprinkler Rough-in12/14/201512/15/201512/15/2015 8:39:30 AMAPASS
Rough to cover inspection complete, approved for cover