Inspections for the day of: Thursday, December 15, 2016.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTom Saunders
TitleELE-INSPECTOR
Phone #208-794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-02275 ELE-Aging Inspection12/15/201612/15/201612/15/2016 2:29:42 PM DONE
still under construction
ELE16-02883 Final12/15/201612/15/201612/15/2016 2:28:49 PMPFAIL
Tyler Phone #: ###-####...

Both dishwasher circuits or circuit need breaker lockouts installed

oven circuit needs breaker lockout installed

panel for addition needs labelling

all new outlets installed shall be of tamper resistant type

future 30a 240v circuit needs to be put on a 2-pole breaker to turn off both circuits simultaneously

A final inspection can not be done until building permit hold is satisfied with city of boise
ELE16-03079 Final12/15/201612/15/201612/15/2016 11:53:57 AMPPASS
JR Phone #: ###-####...

ok to final
ELE16-03139 Final12/15/201612/15/201612/15/2016 11:02:03 AMPPASS
Phone #: ###-#### Inspection requested via web by Matthew White...

ok to final
ELE16-04034 Final12/14/201612/15/201612/15/2016 11:01:21 AMAPASS
Lockbox code on door 2730 home is vacant Phone #: ###-#### Inspection requested via web by shane miller...

ok to final
ELE16-03020 Final12/14/201612/15/201612/15/2016 9:51:05 AMAPASS
Any questions please let me know, the access code is 6949, thx, TW Phone #: ###-#### Inspection requested via web by Stephen Kren...

ok to final
ELE16-03204 Final12/14/201612/15/201612/15/2016 9:50:32 AMAPASS
Any questions please let me know, the access code is 6949, thx, TW Phone #: ###-#### Inspection requested via web by Stephen Kren..

ok to final
ELE16-03402 Final12/14/201612/15/201612/15/2016 9:01:28 AMAPASS
JR Phone #: ###-####....

ok to final
ELE16-04036 Electrical Rough-In12/14/201612/15/201612/15/2016 8:29:00 AMAPASS
Phone #: ###-#### Inspection requested via web by Jim Williams....

ok to cover...wall/ceiling
ELE16-04025 Electrical Rough-In12/15/201612/15/201612/15/2016 12:00:00 AMPCANC
Wall inspection please Phone #: ###-#### >> Inspection requested via web by Celinda Winters-building permit is not picked up yet
ELE16-03544 Final12/14/201612/15/201612/14/2016 4:10:28 PMAPASS
code 1234 Phone #: ###-#### Inspection requested via web by Bob Glenn....

ok to final