Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD16-02720 FIRE-Final Inspection12/14/201612/15/201612/15/2016 2:36:55 PMPFAIL
Provide as-builts to plan review showing the new fences and gates. The vehicle gate to be 20' min. clearance and the a new man gate to be provided at the west side fence. Provide fire dept access/fire lane signage at both property entrances as discussed. All other items ok. As per plan review the knox key at the west property entry and narrow width has been approved by the fire dept.
FIR16-00617 INSP-Final Inspection12/12/201612/15/201612/15/2016 10:28:11 AMAFAIL
The notification devices functioned correctly. I had Brian field adjust two to meet spacing requirements for room method. As-builts required. We started to test the fire/smoke dampers and found that not all are accessible and atleast two have been wired backwards.