BLD16-04434
| FIRE-Final Inspection | 12/15/2016 | 12/15/2016 | 12/15/2016 3:52:15 PM | P | PASS |
|
|
No fire sprinkler modifications, no fire alarm modifications, fire extinguishers are in place with current inspection tags. Final lfe fire safety inspection passed/complete.
|
FIR16-00305
| INSP-Sprinkler Rough-in/Hydro | 12/14/2016 | 12/15/2016 | 12/15/2016 3:52:14 PM | P | PART |
|
|
Hydrostatic test complete for levels 1, 2 and 3 as well as west standpipe.
|
FIR16-00088
| INSP-Sprinkler Rough-in | 12/14/2016 | 12/15/2016 | 12/15/2016 1:35:46 PM | A | PART |
|
|
Soffit inspection for level 5 complete, soffit's approved for cover. Tenting will require modifications before cover will be approved.
|
FIR16-00494
| INSP-Sprinkler Rough-in/Hydro | 12/15/2016 | 12/15/2016 | 12/15/2016 11:39:04 AM | P | PART |
|
|
24 dry air system started with 40psi @ 11:00AM. Rough to cover inspection complete for hardlids, cover approved for hardlids.
|
BLD15-02772
| FIRE-Final Inspection | 12/14/2016 | 12/15/2016 | 12/15/2016 11:26:59 AM | P | PART |
|
|
Partial life fire safety inspection complete for TCO, fire sprinkler inspection complete, fire alarm inspection complete, fire extinguishers are in place with current inspection tags, emergency lighting including exit discharge has been inspected, knox box is in place. Fuel island is still under construction, fuel island is under this permit and will be inspected when completed. Paint booth is to be built at a later date, paint booth has an FIR permit associated with the fire sprinklers that will remain in issued status until paint booth is complete (FIR16-00716) Exit sign that is in place for the paint shop exit is temporary, permanent exit sign for this area is on order, will verify install at a later date. Fire hydrants located on the northwest and southwestside of compound will need to be rotated so the large discharge is not pointing at bollards, fire hydrant rotation will be verified during permanet CO inspection.
|
BLD15-03937
| FIRE-Final Inspection | 12/14/2016 | 12/15/2016 | 12/15/2016 11:18:47 AM | P | PASS |
|
|
Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguishers are in place with current inspection tags. Final life fire safety inspection passed/complete.
|
BLD15-03938
| FIRE-Final Inspection | 12/14/2016 | 12/15/2016 | 12/15/2016 11:17:43 AM | P | PASS |
|
|
No fire sprinklers, no fire alarms, fire extinguisher is in place with a current inspection tag. Final life fire safety inspection passed/complete.
|
FIR16-00318
| INSP-Final Inspection | 12/15/2016 | 12/15/2016 | 12/15/2016 10:24:49 AM | A | PASS |
|
|
Final fire alarm inspection passed/complete
|
FIR16-00308
| INSP-Final Inspection | 12/15/2016 | 12/15/2016 | 12/15/2016 10:22:29 AM | P | PASS |
|
|
Final fire alarm inspection passed/complete.
|
FIR16-00308
| INSP-Conference | 12/13/2016 | 12/15/2016 | 12/15/2016 10:20:42 AM | P | DONE |
|
|
Fire conference complete.
|
FIR16-00244
| INSP-Final Inspection | 12/14/2016 | 12/15/2016 | 12/15/2016 10:19:50 AM | A | PASS |
|
|
Final fire sprinkler inspection passed/complete.
|
FIR16-00100
| INSP-Final Inspection | 12/14/2016 | 12/15/2016 | 12/15/2016 10:19:24 AM | A | PASS |
|
|
Final fire sprinkler inspection passed/complete
|