Inspections for the day of: Thursday, December 15, 2016.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD16-04434 FIRE-Final Inspection12/15/201612/15/201612/15/2016 3:52:15 PMPPASS
No fire sprinkler modifications, no fire alarm modifications, fire extinguishers are in place with current inspection tags. Final lfe fire safety inspection passed/complete.
FIR16-00305 INSP-Sprinkler Rough-in/Hydro12/14/201612/15/201612/15/2016 3:52:14 PMPPART
Hydrostatic test complete for levels 1, 2 and 3 as well as west standpipe.
FIR16-00088 INSP-Sprinkler Rough-in12/14/201612/15/201612/15/2016 1:35:46 PMAPART
Soffit inspection for level 5 complete, soffit's approved for cover. Tenting will require modifications before cover will be approved.
FIR16-00494 INSP-Sprinkler Rough-in/Hydro12/15/201612/15/201612/15/2016 11:39:04 AMPPART
24 dry air system started with 40psi @ 11:00AM. Rough to cover inspection complete for hardlids, cover approved for hardlids.
BLD15-02772 FIRE-Final Inspection12/14/201612/15/201612/15/2016 11:26:59 AMPPART
Partial life fire safety inspection complete for TCO, fire sprinkler inspection complete, fire alarm inspection complete, fire extinguishers are in place with current inspection tags, emergency lighting including exit discharge has been inspected, knox box is in place. Fuel island is still under construction, fuel island is under this permit and will be inspected when completed. Paint booth is to be built at a later date, paint booth has an FIR permit associated with the fire sprinklers that will remain in issued status until paint booth is complete (FIR16-00716) Exit sign that is in place for the paint shop exit is temporary, permanent exit sign for this area is on order, will verify install at a later date. Fire hydrants located on the northwest and southwestside of compound will need to be rotated so the large discharge is not pointing at bollards, fire hydrant rotation will be verified during permanet CO inspection.
BLD15-03937 FIRE-Final Inspection12/14/201612/15/201612/15/2016 11:18:47 AMPPASS
Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguishers are in place with current inspection tags. Final life fire safety inspection passed/complete.
BLD15-03938 FIRE-Final Inspection12/14/201612/15/201612/15/2016 11:17:43 AMPPASS
No fire sprinklers, no fire alarms, fire extinguisher is in place with a current inspection tag. Final life fire safety inspection passed/complete.
FIR16-00318 INSP-Final Inspection12/15/201612/15/201612/15/2016 10:24:49 AMAPASS
Final fire alarm inspection passed/complete
FIR16-00308 INSP-Final Inspection12/15/201612/15/201612/15/2016 10:22:29 AMPPASS
Final fire alarm inspection passed/complete.
FIR16-00308 INSP-Conference12/13/201612/15/201612/15/2016 10:20:42 AMPDONE
Fire conference complete.
FIR16-00244 INSP-Final Inspection12/14/201612/15/201612/15/2016 10:19:50 AMAPASS
Final fire sprinkler inspection passed/complete.
FIR16-00100 INSP-Final Inspection12/14/201612/15/201612/15/2016 10:19:24 AMAPASS
Final fire sprinkler inspection passed/complete