Inspections for the day of: Friday, December 15, 2017.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorEric Story
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-04220 Final12/15/201712/15/201712/15/2017 2:53:16 PMPCANC
Inspection for power to be restored. Please call Alloway office at ###-#### for access Phone #: ###-#### Inspection requested via web by steve ragan
Needed p/s
ELE17-04220 Permanent Service12/15/201712/15/201712/15/2017 2:53:09 PMPPASS
Inspection for power to be restored. Please call Alloway office at ###-#### for access Phone #: ###-#### Inspection requested via web by steve ragan
p/s u/g rec ok, no meter needed just turn main on
ELE17-04039 Permanent Service12/15/201712/15/201712/15/2017 2:52:13 PMPPASS
Installed 2 eight foot grounding rods. Morning or afternoon is fine. I''m five minutes away Phone #: ###-#### Inspection requested via web by Gail Hofert
p/s o/h rec ok
ELE17-03442 Electrical Rough-In12/14/201712/15/201712/15/2017 2:51:46 PMPPASS
UG // Jake Phone #: ###-####
Phase 1 underground ok to cover
ELE17-04022 Rough-In Permanent Service12/14/201712/15/201712/15/2017 11:10:40 AMAPASS
Phone #: ###-#### Inspection requested via web by Mike Okamura
Underground to garage ok to cover
p/s u/g n ok
ELE17-04023 Rough-In Permanent Service12/14/201712/15/201712/15/2017 11:10:10 AMAPASS
Phone #: ###-#### Inspection requested via web by Mike Okamura
Underground ok to cover to detached garage
p/s u/g n ok
ELE17-04024 Rough-In Permanent Service12/14/201712/15/201712/15/2017 11:09:33 AMAPASS
Inspection requested via web by Mike Okamura
Underground to garage ok to cover
p/s u/g n ok
ELE17-04021 Rough-In Permanent Service12/14/201712/15/201712/15/2017 11:09:01 AMAPASS
Phone #: ###-#### Inspection requested via web by Mike Okamura
Underground to garage ok to cover
p/s u/g n ok
ELE17-03663 Final12/12/201712/15/201712/15/2017 9:52:04 AMAPASS
Phone #: ###-#### Inspection requested via web by Mike Okamura
Corrections fixed final ok
ELE17-04178 Final12/12/201712/15/201712/15/2017 9:51:36 AMAPASS
Phone #: ###-#### Inspection requested via web by Mike Okamura
Attached garage final ok
ELE17-04191 Permanent Service12/14/201712/15/201712/15/2017 9:23:26 AMAFAIL
Service inspection so service can be re-energized. Unit should be open by 9:00 by general contractor. Phone #: ###-#### Inspection requested via web by David Nelson
110.24 AFC calculation required proir to service being energized.
Need to verify main bonding jumper in main service gear no access inside to see it
ELE17-04214 Electrical Rough-In12/14/201712/15/201712/15/2017 9:00:16 AMAPASS
Luke-partial on the walls only Phone #: ###-####
Remaining walls not framed will be called inn on another date...
Walls and soffits@floor boxes ok to cover, Electricain will remove existing buried receptacles in walls and cut wires of to insure they are dead and not in use....
ELE17-03762 Final12/14/201712/15/201712/15/2017 8:45:08 AMAPASS
All items done, Final ok