ELE17-02858
| Permanent Service | 12/14/2017 | 12/15/2017 | 12/15/2017 1:36:45 PM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bryan Atkins Waited for contractor to post AFCI, P/S U/G N OK
|
ELE17-04057
| Electrical Rough-In | 12/14/2017 | 12/15/2017 | 12/15/2017 9:48:51 AM | A | FAIL |
|
|
Call 30 minutes prior to inspection so I can make sure the door is unlocked inspect new steel stud walls for cover Phone #: ###-#### Inspection requested via web by Steve Craig NEC 330.12 (1) MC cable shall not be installed where subject to physical damage. Along inside 2x4 steel stud door frame. 300.5 shall not install MC cable within 1 1/4 of edge of framing member
|