Inspections for the day of: Thursday, December 16, 1999.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorMarv Burrus
TitleELE
Phone #340-1297
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE99-04453 Electrical Rough-In12/15/199912/16/199912/16/1999 12:00:00 AMAPASS
HEATHER ###-#### CONFERENCE Conference: branch circuit requirements; grounding/bonding.
ELE99-03871 Final12/15/199912/16/199912/16/1999 12:00:00 AMAPASS
FN ###-####-STAN Meter/main service panel; room-addition completion.
ELE99-03992 Final12/15/199912/16/199912/16/1999 12:00:00 AMAPASS
MARV ###-#### Completion.
ELE99-04251 Final12/15/199912/16/199912/16/1999 12:00:00 AMAPASS
MARV ###-#### Completion.
ELE99-04482 Permanent Service12/16/199912/16/199912/16/1999 12:00:00 AMPFAIL
per. craig ###-#### final - water pipe bond comes from inside. NEC:250-50. Metal water pipe shall be grounded. NEC:250-104. Metal gas pipe shall be bonded. BCC: Junction box shall have secured cover plate.
ELE99-03824 Final12/16/199912/16/199912/16/1999 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 12/16/1999 at 10:58:08. Contact: ###-####. Completion.
ELE99-03824 Permanent Service12/16/199912/16/199912/16/1999 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 12/16/1999 at 11:01:50. Contact: ###-####. Completion- branch circuit connections; final.
ELE99-03955 Electrical Rough-In12/16/199912/16/199912/16/1999 12:00:00 AMPPART
Main/meter service connection for power only corrections posted for sub-panel. NEC:250-50; NEC:250-104; others