BLD03-00589
| FIRE-Final Inspection | 12/15/2003 | 12/16/2003 | 12/16/2003 12:00:00 AM | A | PASS |
|
|
stan wiggins; Phone #: ###-#### Internet Inspection Request from: Barbara Moore per architect the occupant load in bar and back dining area require one exit and the two exits from the main dining area are adequate 12/16/2003 10:14:13 AM
|
BLD03-02283
| FIRE-Final Inspection | 12/15/2003 | 12/16/2003 | 12/16/2003 12:00:00 AM | A | PASS |
|
|
Richard; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes
|
FIR03-00075
| INSP-Conference | 12/15/2003 | 12/16/2003 | 12/16/2003 12:00:00 AM | A | PART |
|
|
Jim; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes met with GC and electrical contractor about pull stations in condo units - they aren't shown on approved plans and not required 12/16/2003 10:12:39 AM
|
FIR03-00675
| INSP-Alarm Testing | 12/15/2003 | 12/16/2003 | 12/16/2003 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 12/15/2003 at 3:34:41 PM. Contact: ###-####.
|
FIR03-00568
| INSP-Sprinkler Rough-in | 12/15/2003 | 12/16/2003 | 12/16/2003 12:00:00 AM | P | PASS |
|
|
reviewed resubmittals; okay to cover 12/16/2003 4:03:33 PM
|
BLD02-00199
| FIRE-Conference | 12/16/2003 | 12/16/2003 | 12/16/2003 12:00:00 AM | P | PART |
|
|
pete-- ###-#### location of knox box at remote annunciator - main entrance 12/16/2003 4:09:06 PM
|
FIR03-00559
| INSP-Final Inspection | 12/16/2003 | 12/16/2003 | 12/16/2003 12:00:00 AM | P | FAIL |
|
|
need sign at FDC indicating basement system only; need blue tag at riser
|
BLD03-02277
| FIRE-Final Inspection | 12/16/2003 | 12/16/2003 | 12/16/2003 12:00:00 AM | P | FAIL |
|
|
need lockout on FACP breaker; need sign on FDC for basment system only; need signs on doors to sprinkler controls; need keys in knox box
|