Inspections for the day of: Thursday, December 16, 2004.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00661 INSP-Final Inspection12/16/200412/16/200412/16/2004 12:00:00 AMAPASS
Final okay 12/16/2004 9:48:09 AM
BLD04-01854 FIRE-Final Inspection12/16/200412/16/200412/16/2004 12:00:00 AMAPASS
Final okay for perm occupancy; awaiting resubmittals for fire alarm and will close it out upon receipt 12/16/2004 9:53:55 AM
BLD04-01935 FIRE-Final Inspection12/16/200412/16/200412/16/2004 12:00:00 AMAPASS
Fire final okay 12/16/2004 9:55:45 AM
FIR03-00816 INSP-Final Inspection12/16/200412/16/200412/16/2004 12:00:00 AMAPASS
FIR03-00667 INSP-Final Inspection12/16/200412/16/200412/16/2004 12:00:00 AMAPASS
FIR04-00662 INSP-Final Inspection12/16/200412/16/200412/16/2004 12:00:00 AMPPART
Scheduled by a contractor via Hello! on 12/16/2004 at 10:39:26 AM. Contact: ###-####. SE office area okay; aux drains will not be piped to exterior per Bill A.; awaiting west side of building to be completed for heads under stairs 12/16/2004 1:09:11 PM
BLD04-00217 FIRE-Final Inspection12/16/200412/16/200412/16/2004 12:00:00 AMPPASS
Kent; Phone #: ###-#### Internet Inspection Request from: Jan Rice GC said owner was to have the address changed to Front St 12/16/2004 4:10:37 PM
FIR04-00578 INSP-Final Inspection12/16/200412/16/200412/16/2004 12:00:00 AMPCANC
Scheduled by a contractor via Hello! on 12/16/2004 at 11:27:32 AM. Contact: ###-####. Rescheduled for 10 am on 12/17 12/16/2004 12:05:15 PM
FIR04-00662 INSP-Final Inspection12/16/200412/16/200412/16/2004 12:00:00 AMPPASS
The permit is okay for final; the west side of building is under a different permit for shell and core 12/16/2004 1:16:32 PM
FIR04-00713 INSP-Final Inspection12/15/200412/16/200412/16/2004 12:00:00 AMPFAIL
Rick, Please call us as soon as you know an approximate time that we can test this floor out at River Quarry building. The office number is ###-####, and my cell is ###-####. Thanks, Jason; Phone #: ###-#### Internet Inspection Request from: Jason Minnick EOL reading on new circuits were below 21.6 volts - appears to be battery problems; will need to retest circuits when batteries are replaced 12/16/2004 2:40:49 PM
BLD04-02377 FIRE-Final Inspection12/15/200412/16/200412/16/2004 12:00:00 AMPPASS
###-#### - mike Fire/life safety okay for final 12/16/2004 2:59:57 PM