BLD05-02802
| BLD-Final | 12/16/2005 | 12/16/2005 | 12/16/2005 4:39:16 PM | P | FAIL |
|
|
Repair existing emergency light, provide approved door hardware at restroom, install tactile sign when delivered.
|
BLD05-01731
| FIRE-Final Inspection | 12/15/2005 | 12/16/2005 | 12/16/2005 4:01:25 PM | A | PASS |
|
|
Fire life safety passed final inspection, NOTE: need to maintain 3' clearance around existing fire hydrant at main entrance off Shoreline Dr per requirements.
|
FIR05-00493
| INSP-Final Inspection | 12/15/2005 | 12/16/2005 | 12/16/2005 3:25:28 PM | A | PART |
|
|
All items are satisfactory except an obstructed head in the 2nd level bonus room is blocked by a surface mounted light, final pending relocation of light fixture or relocate head.
|
FIR05-00843
| INSP-Final Inspection | 12/15/2005 | 12/16/2005 | 12/16/2005 1:35:10 PM | P | PASS |
|
|
Fire sprinkler work is satisfactory, permit finaled.
|
FIR05-00715
| INSP-Final Inspection | 12/15/2005 | 12/16/2005 | 12/16/2005 11:54:59 AM | P | PART |
|
|
Final pending related shell alarm permit final.
|
BLD05-01480
| FIRE-Final Inspection | 12/15/2005 | 12/16/2005 | 12/16/2005 11:47:40 AM | A | NR |
|
|
Related fire alarm permit must be finaled prior to fire life safety final.
|
BLD05-01478
| FIRE-Final Inspection | 12/15/2005 | 12/16/2005 | 12/16/2005 11:41:04 AM | A | NR |
|
|
Related fire alarm permit must be finaled prior to fire life safety final.
|
BLD04-02409
| FIRE-Final Inspection | 12/15/2005 | 12/16/2005 | 12/16/2005 11:39:56 AM | A | NR |
|
|
Associated fire alarm permit must be finaled prior to life safety final.
|
FIR05-00774
| INSP-Final Inspection | 12/15/2005 | 12/16/2005 | 12/16/2005 11:34:25 AM | A | FAIL |
|
|
No final until all ceiling tile and escutcheons are installed, rough-in defficiencies include one office supplying three heads off a 1" line, three areas in which heads are too close to heat diffusers for temp. rating installed, possible obstruction in the womens restroom at stall divider, one office in the existing area is currently being used for storage, heads at this location are spaced for light hazard.
|
FIR05-00089
| INSP-Final Inspection | 12/13/2005 | 12/16/2005 | 12/16/2005 9:55:16 AM | A | PASS |
|
|
Fire sprinkler passed final inspection, defficient items have been completed.
|
FIR05-00038
| INSP-Final Inspection | 12/16/2005 | 12/16/2005 | 12/16/2005 9:53:38 AM | A | PASS |
|
|
UG fire supply passed inspection.
|
MIS05-00229
| FIR-Final | 12/15/2005 | 12/16/2005 | 12/16/2005 8:56:22 AM | A | PASS |
|
|
Fire life safety passed inspection, c/n items have been completed.
|
BLD05-03085
| FIRE-Final Inspection | 12/16/2005 | 12/16/2005 | 12/16/2005 12:00:00 AM | P | PASS |
|
|
Fire life safety is acceptable.
|