Inspections for the day of: Friday, December 16, 2005.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD05-02802 BLD-Final12/16/200512/16/200512/16/2005 4:39:16 PMPFAIL
Repair existing emergency light, provide approved door hardware at restroom, install tactile sign when delivered.
BLD05-01731 FIRE-Final Inspection12/15/200512/16/200512/16/2005 4:01:25 PMAPASS
Fire life safety passed final inspection, NOTE: need to maintain 3' clearance around existing fire hydrant at main entrance off Shoreline Dr per requirements.
FIR05-00493 INSP-Final Inspection12/15/200512/16/200512/16/2005 3:25:28 PMAPART
All items are satisfactory except an obstructed head in the 2nd level bonus room is blocked by a surface mounted light, final pending relocation of light fixture or relocate head.
FIR05-00843 INSP-Final Inspection12/15/200512/16/200512/16/2005 1:35:10 PMPPASS
Fire sprinkler work is satisfactory, permit finaled.
FIR05-00715 INSP-Final Inspection12/15/200512/16/200512/16/2005 11:54:59 AMPPART
Final pending related shell alarm permit final.
BLD05-01480 FIRE-Final Inspection12/15/200512/16/200512/16/2005 11:47:40 AMANR
Related fire alarm permit must be finaled prior to fire life safety final.
BLD05-01478 FIRE-Final Inspection12/15/200512/16/200512/16/2005 11:41:04 AMANR
Related fire alarm permit must be finaled prior to fire life safety final.
BLD04-02409 FIRE-Final Inspection12/15/200512/16/200512/16/2005 11:39:56 AMANR
Associated fire alarm permit must be finaled prior to life safety final.
FIR05-00774 INSP-Final Inspection12/15/200512/16/200512/16/2005 11:34:25 AMAFAIL
No final until all ceiling tile and escutcheons are installed, rough-in defficiencies include one office supplying three heads off a 1" line, three areas in which heads are too close to heat diffusers for temp. rating installed, possible obstruction in the womens restroom at stall divider, one office in the existing area is currently being used for storage, heads at this location are spaced for light hazard.
FIR05-00089 INSP-Final Inspection12/13/200512/16/200512/16/2005 9:55:16 AMAPASS
Fire sprinkler passed final inspection, defficient items have been completed.
FIR05-00038 INSP-Final Inspection12/16/200512/16/200512/16/2005 9:53:38 AMAPASS
UG fire supply passed inspection.
MIS05-00229 FIR-Final12/15/200512/16/200512/16/2005 8:56:22 AMAPASS
Fire life safety passed inspection, c/n items have been completed.
BLD05-03085 FIRE-Final Inspection12/16/200512/16/200512/16/2005 12:00:00 AMPPASS
Fire life safety is acceptable.