Inspections for the day of: Tuesday, December 16, 2008.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00500 INSP-Sprinkler Rough-in/Hydro12/15/200812/16/200812/16/2008 5:36:01 PMPPASS
The remaining hydro tests passed.
FIR08-00647 INSP-Final Inspection12/12/200812/16/200812/16/2008 3:13:54 PMPPART
The underground supply flush passed.
BLD08-00424 FIRE-Final Inspection12/16/200812/16/200812/16/2008 3:12:36 PMPPASS
Life safety passed.
FIR08-00341 INSP-Alarm Testing12/15/200812/16/200812/16/2008 3:12:11 PMADONE
See the city approved plans for devices tested. The audio/visuals were also tested. The interconnections between the NAC panels tested ok. The existing NAC panel in the mechanical room needs 12.7 ah batteries. Supervision failed on the 110ah battery backup.
BLD07-01845 FIRE-Final Inspection12/15/200812/16/200812/16/2008 11:38:23 AMAPART
The dining area is ok to occupy.