FIR13-00725
| INSP-Sprinkler Rough-in | 12/15/2014 | 12/16/2014 | 12/17/2014 11:30:13 AM | P | PART |
|
|
Completed rough-in inspection at the 5th floor level plan sheet FP-18. Items noted include; blocked upright coverage at an electrical room, EC upright in contact with a wall, separation distance at two EC uprights is not met, drum drip at the dry system remote end is not accessible, field modifications at remote area 3 include an additional branchline and added pendent heads at the perimeter soffits, provide label at relocated dry system inspectors test, construction at the elevator lobby bay doors and concealed space incomplete, need to remove foil at uprights once painting is finished. Refer to dated plan annotations.
|
NAF14-00026
| INSP-Final | 12/16/2014 | 12/16/2014 | 12/16/2014 4:51:15 PM | P | PASS |
|
|
Fire sprinkler work completed and passed both rough-in and final inspections. Permit final okayed.
|
BLD14-02773
| FIRE-Final Inspection | 12/15/2014 | 12/16/2014 | 12/16/2014 1:54:52 PM | A | PART |
|
|
Final pending project related fire alarm work to connect a duct smoke detector at an RTU not yet installed. ok for temp c of o
|
BLD14-03433
| FIRE-Final Inspection | 12/15/2014 | 12/16/2014 | 12/16/2014 11:25:43 AM | A | FAIL |
|
|
C/N items include; provide approved hardware at the main entry/exit, post "door to remain..." signage per review documents.
|
BLD14-03167
| FIRE-Final Inspection | 12/15/2014 | 12/16/2014 | 12/16/2014 11:24:13 AM | P | PASS |
|
|
Site verified noted corrections. Life safety passed.
|
BLD14-01301
| FIRE-Final Inspection | 12/15/2014 | 12/16/2014 | 12/16/2014 11:23:16 AM | A | PASS |
|
|
Noted correction items verified for completion. Fire life safety finaled.
|
BLD14-03493
| FIRE-Final Inspection | 12/15/2014 | 12/16/2014 | 12/16/2014 11:22:27 AM | A | PASS |
|
|
Items to be finished prior to final include; post correct size address numbers, remove or blank keyed lock deadbolts at two locations. Remainder of inspection items passed.
|