FIR14-00474 INSP-Sprinkler Rough-in/Hydro12/16/201412/16/201412/16/2014 3:31:37 PMPPASS
North east room ceiling ok to install.
FIR14-00578 INSP-Sprinkler Rough-in12/15/201412/16/201412/16/2014 3:23:08 PMPFAIL
Tenting has not been repaired. Piping can not be covered.
BLD14-03394 FIRE-Final Inspection12/15/201412/16/201412/16/2014 2:59:24 PMPPASS
Life safety passed
FIR14-00574 INSP-Sprinkler Rough-in/Hydro12/15/201412/16/201412/16/2014 2:35:56 PMAFAIL
Overhead hydro test failed on both systems due to visible loss of pressure on the guages.
BLD14-03342 FIRE-Final Inspection12/15/201412/16/201412/16/2014 1:40:08 PMAPART
As per the approved scope of work the Kitchen/service area life/safety is approved.. A plan modification is needed showing the adjacent seating area on the raised platform. A termporary occupancy for life safety is being given per conversation with scott and jason.
GCB14-00110 FIRE-Final Inspection12/12/201412/16/201412/16/2014 12:57:57 PMPPART
A temporary occupancy is being given with Scott's permission until the hood suppression system has been interconnected to the existing fire alarm system. A permit is required for this work. I also requested additional emergency lighting in the corridor infront of the restrooms. Temporary Occupancy approval until 1/16/15.
NAF14-00027 INSP-Final12/15/201412/16/201412/16/2014 12:54:08 PMAPART
Hood suppression system functioned correctly but needs connected to the existing fire alarm system
BLD13-02726 FIRE-Final Inspection12/15/201412/16/201412/16/2014 10:27:59 AMAPASS
Life safety passed
FIR14-00871 INSP-Sprinkler Rough-in12/15/201412/16/201412/16/2014 10:06:29 AMAPASS
See the city approved plans for rooms marked ok where the sprinkler piping is ok to cover.
BLD14-03469 FIRE-Final Inspection12/15/201412/16/201412/16/2014 9:07:31 AMAFAIL
Provide annual inspection for the fire extinguisher, remove the thumbturn deadbolt (keyed ok) from the main exit and provide sticker
BLD14-02226 FIRE-Final Inspection12/12/201412/16/201412/16/2014 8:41:48 AMAPART
A life safety temporary was given until a strobe is added in the open office. All other life safety items appear ok.
FIR14-00720 INSP-Final Inspection12/16/201412/16/201412/16/2014 8:40:50 AMAPART
A temporary was given until tomorrow when the additional strobe is added in the open office area. Need as-builts submitted.