Inspections for the day of: Wednesday, December 16, 2015.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR15-00828 INSP-Sprinkler Rough-in/Hydro12/15/201512/16/201512/16/2015 2:56:31 PMPPASS
underground flush passed on both risers. Remaining underground piping is ok to cover.
BLD15-04238 FIRE-Final Inspection12/16/201512/16/201512/16/2015 2:06:57 PMPPASS
life safety passed
BLD15-04262 FIRE-Final Inspection12/16/201512/16/201512/16/2015 1:29:47 PMPFAIL
Remove the thumbturn dead bolt on the warehouse door and provide single action type, repair the exit sign and emergency light in the warehouse, provide annual inspection tag for the fire extinguisher, provide sticker and automatic flush bolts for the main exit, delete the other main exit or provide ADA compliant hardware (plans state only one of the two front exits is required). Single horn on wall is ok to remain.
BLD15-02842 FIRE-Conference12/15/201512/16/201512/16/2015 10:54:49 AMPDONE
Dutch, myself and the electrician went over fire alarm and fire life safety requirements. It appears additional smoke alarms will be required and additional exit signs/emergency lighting will be required as well.
FIR15-00837 INSP-Sprinkler Rough-in12/15/201512/16/201512/16/2015 10:52:14 AMAPASS
Rough-in passed. Piping can be covered. Upright coveraged added in concealed space.
BLD15-04262 FIRE-Final Inspection12/11/201512/16/201512/16/2015 9:10:54 AMACANC
Left two messages on voice mail, one when I was on the way and the second 25 minutes later when I arrived. No one here and no access.
FIR12-00433 INSP-Final Inspection12/14/201512/16/201512/16/2015 8:54:17 AMAFAIL
Duct smoke detectors tested ok. FOr a final need as-builts submitted to lee for approval showing the different dialer and changed device counts and addresses. Also need to mount the map at the facp.
BLD15-04350 FIRE-Final Inspection12/15/201512/16/201512/16/2015 12:00:00 AMACANC
Bill Phone #: ###-####
FIR15-00618 INSP-Alarm Testing12/14/201512/16/201512/14/2015 5:14:05 PMPCANC
Phone #: ###-#### >> Inspection requested via web by Brian Richard Inspection cancelled from web by: Brian Richard