BLD16-02814
| FIRE-Final Inspection | 12/16/2016 | 12/16/2016 | 12/16/2016 12:06:09 PM | P | PASS |
|
|
life safety passed. Emergency lights and exit signs verified in the existing corridor
|
BLD16-02720
| FIRE-Final Inspection | 12/15/2016 | 12/16/2016 | 12/16/2016 11:38:54 AM | A | PART |
|
|
A 30 day temporary is being given with Scott's permission until the as-builts showing the new fences and gates have approved, and the fences and gates installed/verified.
|
FIR16-00617
| INSP-Alarm Testing | 12/15/2016 | 12/16/2016 | 12/16/2016 11:13:05 AM | P | PASS |
|
|
permit finaled
|
BLD16-03569
| FIRE-Final Inspection | 12/15/2016 | 12/16/2016 | 12/16/2016 8:42:04 AM | A | FAIL |
|
|
Provide suite number, repair all exit signs and emergency lights including in the path of egress, reverse hardware at the connecting corridor, provide annual inspection for the fire extinguisher. Delete the exit sign directing people to the new wall/infill as discussed.
|
BLD16-03568
| FIRE-Final Inspection | 12/15/2016 | 12/16/2016 | 12/16/2016 8:41:49 AM | A | FAIL |
|
|
Provide suite number, repair all exit signs and emergency lights including in the path of egress, reverse hardware at the connecting corridor, provide annual inspection for the fire extinguisher. Delete the exit sign directing people to the new wall/infill as discussed.
|