ELE02-00779
| ELE-Aging Inspection | 12/17/2002 | 12/17/2002 | 12/17/2002 12:00:00 AM | | PART |
|
|
called contractor he said job has been put on hold and to expire permit , he will get a new permit if job starts up again 12/17/2002 2:50:54 PM
|
ELE02-00834
| ELE-Aging Inspection | 12/17/2002 | 12/17/2002 | 12/17/2002 12:00:00 AM | | DONE |
|
|
|
ELE02-01402
| Final | 12/16/2002 | 12/17/2002 | 12/17/2002 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 12/16/2002 at 10:10:10. Contact: ###-####. ok 12/17/2002 12:02:19 PM
|
ELE02-02728
| Electrical Rough-In | 12/16/2002 | 12/17/2002 | 12/17/2002 12:00:00 AM | A | PART |
|
|
for shop to insp panel -gary- ###-####-call 20 min before insp for insulation only 12/17/2002 11:08:12 AM
|
ELE02-03882
| Final | 12/16/2002 | 12/17/2002 | 12/17/2002 12:00:00 AM | A | PASS |
|
|
ALISON ###-#### see added p/s 12/16/2002 4:56:16 PM
|
ELE02-02728
| Permanent Service | 12/17/2002 | 12/17/2002 | 12/17/2002 12:00:00 AM | A | PART |
|
|
p/s o/h rec. ok for house, service at garage will go away
|
ELE02-00488
| Electrical Rough-In | 12/16/2002 | 12/17/2002 | 12/17/2002 12:00:00 AM | A | FAIL |
|
|
MIKE; Phone #: ###-#### Internet Inspection Request from: Darla Downs cor. posted 300.4 nail plates and 11/4 replace 2,3 gang boxes with broken clamps 12/17/2002 1:07:23 PM
|
ELE02-01916
| Electrical Rough-In | 12/16/2002 | 12/17/2002 | 12/17/2002 12:00:00 AM | A | PART |
|
|
conference for extension only ###-#### andy called ok 12/17/2002 12:02:40 PM
|
ELE02-03884
| Rough-In Permanent Service | 12/16/2002 | 12/17/2002 | 12/17/2002 12:00:00 AM | A | FAIL |
|
|
###-#### dennis cor. posted called 314.43 outside boxes, 314.16, 2150.148, kit 3gang, 300.4 nail plates and 11/4, 250.24 terminate GEC at neutral bus not can, 300.14 needs 6" for make up rquip grds 12/17/2002 2:20:42 PM
|
ELE02-03875
| Final | 12/17/2002 | 12/17/2002 | 12/17/2002 12:00:00 AM | P | NH |
|
|
DAWN ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie notice posted called 12/17/2002 3:20:25 PM
|
ELE02-03889
| Permanent Service | 12/17/2002 | 12/17/2002 | 12/17/2002 12:00:00 AM | P | FAIL |
|
|
CALL FIRST ###-#### SCOTT , THIS PERMIT HAS BEEN APPROVED THROUGH TIM AND JENNIFER corrections posted met with owner, 11.26 (A)(1&2)230.6, 230.24(A), 230.28 needs 2" rigid or IMC, and guy kit, 230.72 group service disconnects, 250.90 bond nipple at p/s, 250.52 grd within 5 ft for u/g water pipe, 250.53 needs 2 grd rods, 110.3(B) install only 1 wire under screws at terminals, 312.5(A&C) needs con. for range cable and no exposed range wires allowed in wall 12/17/2002 5:46:27 PM
|
ELE02-03885
| Electrical Rough-In | 12/17/2002 | 12/17/2002 | 12/17/2002 12:00:00 AM | P | PART |
|
|
called contractor shall not use pot metal grd clamps within 18" of dirt needs brass ones, and address WH wiring needs jbox at WH maybe #10 wire, and shall not parallel # 12 feed to WH
|
ELE01-03617
| Final | 12/16/2002 | 12/17/2002 | 12/17/2002 12:00:00 AM | P | PART |
|
|
MIKE ###-#### TEMP WALK WAY temp occupancy only for walkway card signed by JF, and JS 12/17/2002 4:20:55 PM
|
ELE02-03830
| Electrical Rough-In | 12/17/2002 | 12/17/2002 | 12/17/2002 12:00:00 AM | P | PASS |
|
|
###-#### ceiling inspection ok 12/17/2002 5:37:19 PM
|
ELE02-03885
| Permanent Service | 12/17/2002 | 12/17/2002 | 12/17/2002 12:00:00 AM | P | PASS |
|
|
PER SER KENT ###-#### p/s o/h rec. ok
see added r/i inspection 12/17/2002 6:45:10 PM
|