Inspections for the day of: Friday, December 17, 2004.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE04-03948 Final12/16/200412/17/200412/17/2004 12:00:00 AMAPASS
final, talk to Jim Schmere he knows what needs looked at Internet Inspection Request from: Andy Rose ok to final 12/17/2004 8:28:14 AM
ELE04-03939 Rough-In Permanent Service12/16/200412/17/200412/17/2004 12:00:00 AMAPART
Scheduled by a contractor via Hello! on 12/16/2004 at 11:46:46 AM. Contact: ###-####. ufer ok to cover 12/17/2004 9:42:57 AM
ELE04-02458 Final12/16/200412/17/200412/17/2004 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 12/16/2004 at 11:50:29 AM. Contact: ###-####. ok to final 12/17/2004 10:31:24 AM
ELE04-02459 Final12/16/200412/17/200412/17/2004 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 12/16/2004 at 11:52:04 AM. Contact: ###-####. ok to final 12/17/2004 10:11:39 AM
ELE04-02905 Final12/16/200412/17/200412/17/2004 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 12/16/2004 at 11:53:38 AM. Contact: ###-####. ok to final 12/17/2004 10:12:42 AM
ELE04-03922 Temporary Service12/16/200412/17/200412/17/2004 12:00:00 AMACANC
Please contact Dave for any questions; Phone #: ###-#### Internet Inspection Request from: William Zerfas 12/17/2004 10:53:45 AM called contr. pole already set and has sticker for permit #03924 on it and it is already finalled. 12/17/2004 10:55:39 AM
ELE04-03453 Final12/16/200412/17/200412/17/2004 12:00:00 AMAPASS
Corrections completed,please re-inspect.Thanks!!!Dan.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell ok to final 12/17/2004 9:20:45 AM
ELE04-03983 Electrical Rough-In12/17/200412/17/200412/17/2004 12:00:00 AMPPART
uepher ground inspection please////steve ###-#### ok to cover for ufer only 12/17/2004 3:46:43 PM
ELE04-03082 Final12/17/200412/17/200412/17/2004 12:00:00 AMPPASS
don ###-#### overroad condition hold per Bob Archibald 250.104(1) bonding shall be done at water heater. Called and left survey. ok to final 12/17/2004 12:36:57 PM
ELE04-03636 Final12/17/200412/17/200412/17/2004 12:00:00 AMPPASS
Ron; Phone #: ###-#### Internet Inspection Request from: Jan Rice ok to final corrections made 12/17/2004 3:21:54 PM
ELE99-03822 Final12/17/200412/17/200412/17/2004 12:00:00 AMPFAIL
Phone #: ###-#### Internet Inspection Request from: Linda Hartwell 314.15 Outdoor boxes shall be in weatherproof style for lights, receptacles, and switches. 314.20 boxes shall be set back less than 1/4" in wall. 314.27(A) Outlet boxes for light fixtures in the ceiling shall be designed for the purpose. 210.8(A)(1) and(2) Bathroom and garage shall use GFCI type receptacles. 406.5(B) Metal faceplates shall be grounded. 406.4 and 404.10(B) switches and receptacles shall be held rigidly and supplied with covers and installed.110.12(C) Receptacles shall be unbroken. 110.3(B) Receptacles shall be wired correctly 12/17/2004 5:51:09 PM
ELE04-03856 Electrical Rough-In12/17/200412/17/200412/17/2004 12:00:00 AMPPASS
Glen; Phone #: ###-#### Internet Inspection Request from: Jan Rice ok to cover wall and ceiling. South side only. Corrections made. 12/17/2004 1:18:51 PM
ELE04-03995 Final12/17/200412/17/200412/17/2004 12:00:00 AMPFAIL
House addition. 210.52(A)(1) receptacles shall be 12' maximum apart along wall space.210.52(A)(2) receptacles shall be in wall 2' or wider. Owner will open wall for stapling confirmation. 12/17/2004 5:07:34 PM
ELE04-03563 Final12/15/200412/17/200412/16/2004 12:00:00 AMACANC
Final For Occupancy; Phone #: ###-#### Internet Inspection Request from: Rich Rice cancel this inspection, since it was done on 12-16-04. 12/16/2004 9:28:39 AM