ELE04-03948
| Final | 12/16/2004 | 12/17/2004 | 12/17/2004 12:00:00 AM | A | PASS |
|
|
final, talk to Jim Schmere he knows what needs looked at Internet Inspection Request from: Andy Rose ok to final 12/17/2004 8:28:14 AM
|
ELE04-03939
| Rough-In Permanent Service | 12/16/2004 | 12/17/2004 | 12/17/2004 12:00:00 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 12/16/2004 at 11:46:46 AM. Contact: ###-####. ufer ok to cover 12/17/2004 9:42:57 AM
|
ELE04-02458
| Final | 12/16/2004 | 12/17/2004 | 12/17/2004 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 12/16/2004 at 11:50:29 AM. Contact: ###-####. ok to final 12/17/2004 10:31:24 AM
|
ELE04-02459
| Final | 12/16/2004 | 12/17/2004 | 12/17/2004 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 12/16/2004 at 11:52:04 AM. Contact: ###-####. ok to final 12/17/2004 10:11:39 AM
|
ELE04-02905
| Final | 12/16/2004 | 12/17/2004 | 12/17/2004 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 12/16/2004 at 11:53:38 AM. Contact: ###-####. ok to final 12/17/2004 10:12:42 AM
|
ELE04-03922
| Temporary Service | 12/16/2004 | 12/17/2004 | 12/17/2004 12:00:00 AM | A | CANC |
|
|
Please contact Dave for any questions; Phone #: ###-#### Internet Inspection Request from: William Zerfas 12/17/2004 10:53:45 AM called contr. pole already set and has sticker for permit #03924 on it and it is already finalled. 12/17/2004 10:55:39 AM
|
ELE04-03453
| Final | 12/16/2004 | 12/17/2004 | 12/17/2004 12:00:00 AM | A | PASS |
|
|
Corrections completed,please re-inspect.Thanks!!!Dan.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell ok to final 12/17/2004 9:20:45 AM
|
ELE04-03983
| Electrical Rough-In | 12/17/2004 | 12/17/2004 | 12/17/2004 12:00:00 AM | P | PART |
|
|
uepher ground inspection please////steve ###-#### ok to cover for ufer only 12/17/2004 3:46:43 PM
|
ELE04-03082
| Final | 12/17/2004 | 12/17/2004 | 12/17/2004 12:00:00 AM | P | PASS |
|
|
don ###-#### overroad condition hold per Bob Archibald 250.104(1) bonding shall be done at water heater. Called and left survey. ok to final 12/17/2004 12:36:57 PM
|
ELE04-03636
| Final | 12/17/2004 | 12/17/2004 | 12/17/2004 12:00:00 AM | P | PASS |
|
|
Ron; Phone #: ###-#### Internet Inspection Request from: Jan Rice ok to final corrections made 12/17/2004 3:21:54 PM
|
ELE99-03822
| Final | 12/17/2004 | 12/17/2004 | 12/17/2004 12:00:00 AM | P | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Linda Hartwell 314.15 Outdoor boxes shall be in weatherproof style for lights, receptacles, and switches. 314.20 boxes shall be set back less than 1/4" in wall. 314.27(A) Outlet boxes for light fixtures in the ceiling shall be designed for the purpose. 210.8(A)(1) and(2) Bathroom and garage shall use GFCI type receptacles. 406.5(B) Metal faceplates shall be grounded. 406.4 and 404.10(B) switches and receptacles shall be held rigidly and supplied with covers and installed.110.12(C) Receptacles shall be unbroken. 110.3(B) Receptacles shall be wired correctly 12/17/2004 5:51:09 PM
|
ELE04-03856
| Electrical Rough-In | 12/17/2004 | 12/17/2004 | 12/17/2004 12:00:00 AM | P | PASS |
|
|
Glen; Phone #: ###-#### Internet Inspection Request from: Jan Rice ok to cover wall and ceiling. South side only. Corrections made. 12/17/2004 1:18:51 PM
|
ELE04-03995
| Final | 12/17/2004 | 12/17/2004 | 12/17/2004 12:00:00 AM | P | FAIL |
|
|
House addition. 210.52(A)(1) receptacles shall be 12' maximum apart along wall space.210.52(A)(2) receptacles shall be in wall 2' or wider. Owner will open wall for stapling confirmation. 12/17/2004 5:07:34 PM
|
ELE04-03563
| Final | 12/15/2004 | 12/17/2004 | 12/16/2004 12:00:00 AM | A | CANC |
|
|
Final For Occupancy; Phone #: ###-#### Internet Inspection Request from: Rich Rice cancel this inspection, since it was done on 12-16-04. 12/16/2004 9:28:39 AM
|