Inspections for the day of: Friday, December 17, 2004.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD04-02635 FIRE-Final Inspection12/16/200412/17/200412/17/2004 12:00:00 AMAPART
A temporary occuapancy was given. Fire extinguisher needs mounted, mount knox key box and provide suite number 12/17/2004 8:44:20 AM
BLD04-01016 FIRE-Final Inspection12/16/200412/17/200412/17/2004 12:00:00 AMAPASS
Fire life safety finaled 12/17/2004 9:57:40 AM
BLD04-01894 FIRE-Final Inspection12/16/200412/17/200412/17/2004 12:00:00 AMAPASS
Fire life safety finaled 12/17/2004 9:07:29 AM
FIR04-00758 INSP-Sprinkler Rough-in/Hydro12/17/200412/17/200412/17/2004 12:00:00 AMAPASS
Sprinklers ok to cover 12/17/2004 8:19:15 AM
FIR04-00741 INSP-Sprinkler Rough-in/Hydro12/17/200412/17/200412/17/2004 12:00:00 AMAPASS
Sprinklers ok to cover 12/17/2004 8:19:25 AM
BLD04-00960 FIRE-Final Inspection12/17/200412/17/200412/17/2004 12:00:00 AMPPASS
Fire life safety finaled 12/17/2004 2:57:45 PM
BLD04-02122 FIRE-Final Inspection12/17/200412/17/200412/17/2004 12:00:00 AMPPASS
fire life safety finaled 12/17/2004 4:19:30 PM
FIR04-00677 INSP-Final Inspection12/17/200412/17/200412/17/2004 12:00:00 AMPPASS
fire sprinklers finaled
FIR03-00012 INSP-Final Inspection12/16/200412/17/200412/17/2004 12:00:00 AMPFAIL
Need two a/v's relocated to within 15' of the end of the corridor on the third floor and in the basement. Replace the door holder on the first floor and provide as builts. 12/17/2004 1:49:24 PM
FIR03-00586 INSP-Final Inspection12/16/200412/17/200412/17/2004 12:00:00 AMPFAIL
Battery calcs, flow switch, battery supervision and smoke detectors on the east side of building (5 total) operate correctly. Inspection stopped after finding the items listed. The monitoring company is not getting all of the signals sent such as Phone line 1 and low battery. Smoke detectors on the west half of the building annunciate locally but do not report to the panel. The tamper switches supervisory signal is latching and is not supposed to per nfpa 72 4.4.3.2.4. Per the manufacturer the panel can't be reprogrammed. 12/17/2004 1:56:55 PM
BLD04-01729 FIRE-Final Inspection12/16/200412/17/200412/17/2004 12:00:00 AMPPASS
Fire life safety finaled 12/17/2004 3:54:46 PM
FIR04-00675 INSP-Alarm Testing12/16/200412/17/200412/17/2004 12:00:00 AMPPASS
Fire alarm finaled 12/17/2004 2:40:01 PM