BLD04-02635
| FIRE-Final Inspection | 12/16/2004 | 12/17/2004 | 12/17/2004 12:00:00 AM | A | PART |
|
|
A temporary occuapancy was given. Fire extinguisher needs mounted, mount knox key box and provide suite number 12/17/2004 8:44:20 AM
|
BLD04-01016
| FIRE-Final Inspection | 12/16/2004 | 12/17/2004 | 12/17/2004 12:00:00 AM | A | PASS |
|
|
Fire life safety finaled 12/17/2004 9:57:40 AM
|
BLD04-01894
| FIRE-Final Inspection | 12/16/2004 | 12/17/2004 | 12/17/2004 12:00:00 AM | A | PASS |
|
|
Fire life safety finaled 12/17/2004 9:07:29 AM
|
FIR04-00758
| INSP-Sprinkler Rough-in/Hydro | 12/17/2004 | 12/17/2004 | 12/17/2004 12:00:00 AM | A | PASS |
|
|
Sprinklers ok to cover 12/17/2004 8:19:15 AM
|
FIR04-00741
| INSP-Sprinkler Rough-in/Hydro | 12/17/2004 | 12/17/2004 | 12/17/2004 12:00:00 AM | A | PASS |
|
|
Sprinklers ok to cover 12/17/2004 8:19:25 AM
|
BLD04-00960
| FIRE-Final Inspection | 12/17/2004 | 12/17/2004 | 12/17/2004 12:00:00 AM | P | PASS |
|
|
Fire life safety finaled 12/17/2004 2:57:45 PM
|
BLD04-02122
| FIRE-Final Inspection | 12/17/2004 | 12/17/2004 | 12/17/2004 12:00:00 AM | P | PASS |
|
|
fire life safety finaled 12/17/2004 4:19:30 PM
|
FIR04-00677
| INSP-Final Inspection | 12/17/2004 | 12/17/2004 | 12/17/2004 12:00:00 AM | P | PASS |
|
|
fire sprinklers finaled
|
FIR03-00012
| INSP-Final Inspection | 12/16/2004 | 12/17/2004 | 12/17/2004 12:00:00 AM | P | FAIL |
|
|
Need two a/v's relocated to within 15' of the end of the corridor on the third floor and in the basement. Replace the door holder on the first floor and provide as builts. 12/17/2004 1:49:24 PM
|
FIR03-00586
| INSP-Final Inspection | 12/16/2004 | 12/17/2004 | 12/17/2004 12:00:00 AM | P | FAIL |
|
|
Battery calcs, flow switch, battery supervision and smoke detectors on the east side of building (5 total) operate correctly. Inspection stopped after finding the items listed. The monitoring company is not getting all of the signals sent such as Phone line 1 and low battery. Smoke detectors on the west half of the building annunciate locally but do not report to the panel. The tamper switches supervisory signal is latching and is not supposed to per nfpa 72 4.4.3.2.4. Per the manufacturer the panel can't be reprogrammed. 12/17/2004 1:56:55 PM
|
BLD04-01729
| FIRE-Final Inspection | 12/16/2004 | 12/17/2004 | 12/17/2004 12:00:00 AM | P | PASS |
|
|
Fire life safety finaled 12/17/2004 3:54:46 PM
|
FIR04-00675
| INSP-Alarm Testing | 12/16/2004 | 12/17/2004 | 12/17/2004 12:00:00 AM | P | PASS |
|
|
Fire alarm finaled 12/17/2004 2:40:01 PM
|