Inspections for the day of: Monday, December 17, 2007.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-03227 ELE-Aging Inspection12/17/200712/17/200712/20/2007 4:27:22 PM DONE
ELE07-03241 Final12/17/200712/17/200712/17/2007 3:55:53 PMPNR
All we have left is the point of sale they would like to move in merchindise this week so could you please do a final on all but point of sale Phone #: ###-#### Internet Inspection Request from: Scott Abbott
talked with contr job not ready also needs listed fan boxes for paddle fans
ELE07-04122 Temporary Service12/17/200712/17/200712/17/2007 2:53:34 PMPPASS
###-#### Internet Inspection Request from: Todd Holbrook t/s u/g new ok
ELE07-03762 Final12/17/200712/17/200712/17/2007 2:22:40 PMPFAIL
kitchen remodel final
Contact: James Cox Phone #: ###-#### Internet Inspection Request from: HARVEY REYNA called corr. 110.3(B) shall use manufactures listed breakers only, B C C all wiring shall be complete range hood
ELE07-03320 Final12/17/200712/17/200712/17/2007 1:43:09 PMPFAIL
lock box code is GIB Phone #: ###-#### Internet Inspection Request from: Sean Peltier corr called shall bond all metallic water systems and bond around isolated sections sized to T250.66
ELE07-04141 Permanent Service12/17/200712/17/200712/17/2007 12:43:50 PMPPASS
ron Phone #: ###-#### p/s o/h rec. ok
ELE07-01722 ELE-Aging Inspection12/17/200712/17/200712/17/2007 10:28:15 AM PART
wsuc
ELE07-03854 Final12/16/200712/17/200712/17/2007 10:01:31 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Curtis Dunham ok card signed
ELE07-00458 Final12/15/200712/17/200712/17/2007 9:23:46 AMAFAIL
Front Door Open, other trades may be on site. Owners (Mark & Debra) live next door @ 1812 Lemp. Phone #: ###-#### Internet Inspection Request from: David Seilheimer corr fee due called left message
210.52(A) needs outlets for wall space back bed rm upstairs right of closet, downstairs south bed rm left of closet, 200.11 reversed polarity south upstairs bed rm left of front window, 406.4(A B D) recepts loose and set back in plates, 408.4 be specific purpose and use
ELE07-04124 Electrical Rough-In12/14/200712/17/200712/17/2007 8:33:30 AMAFAIL
Contact is Jay Sprik. Clubhouse at the Quail Hollow Golf Course. Phone #: ###-#### Internet Inspection Request from: Richard Montgomery called left message no response wrong address