Inspections for the day of: Monday, December 17, 2007.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00937 INSP-Sprinkler Rough-in12/17/200712/17/200712/18/2007 11:00:29 AMPNR
bruce - please call 1/2 hr prior to inspection Phone #: ###-####
BLD07-02303 FIRE-Final Inspection12/17/200712/17/200712/18/2007 9:58:01 AMPPASS
Life safety inspection passed.
BLD06-01518 FIRE-Final Inspection12/14/200712/17/200712/18/2007 8:53:39 AMAPASS
All corrections made per last inspection.KR
FIR07-00992 INSP-Sprinkler Rough-in/Hydro12/17/200712/17/200712/17/2007 3:13:55 PMPPART
OH system modifications are approved for cover at the drop ceilings.
FIR07-00882 INSP-Final Inspection12/17/200712/17/200712/17/2007 2:50:59 PMPPASS
Corrections verified, per GC the closet at the SW side of the tenant area is to be constructed as well as the soffit at the NW corner.
FIR07-00606 INSP-Conference12/17/200712/17/200712/17/2007 2:46:43 PMPDONE
Inspection to verify seismic restraints for beam clamp hanger attatchments for the cafeteria area prior to fireproofing.
FIR07-00039 INSP-Final Inspection12/14/200712/17/200712/17/2007 1:09:32 PMAFAIL
Cannot be finaled due to missing escutcheons at all areas, noted heads at some locations have been painted and will need to be replaced, no other items reviewed at this time.
FIR07-00023 INSP-Final Inspection12/14/200712/17/200712/17/2007 1:06:43 PMAFAIL
As-built plans for this project were not provided.
FIR07-00038 INSP-Final Inspection12/14/200712/17/200712/17/2007 1:03:34 PMAPASS
Required corrections have been completed, fire sprinkler permit finaled.
FIR07-00040 INSP-Final Inspection12/14/200712/17/200712/17/2007 1:02:34 PMANR
Jobsite is not in condition for a final inspection, not all areas could be accessed due to floor tile installation, missing light fixtures for verification of correct spacing, painting in progress.
FIR07-00037 INSP-Final Inspection12/14/200712/17/200712/17/2007 1:00:02 PMAFAIL
As-built plans are not accurate, one head is shown with no piping attatched, two heads are spaced incorrecty, missing head located in a closet next to the front door.
FIR07-00030 INSP-Final Inspection12/14/200712/17/200712/17/2007 12:58:10 PMAFAIL
As-built plans do not match field install, see branch line located in a wall adjacent to a closet missing coverage.
FIR07-00024 INSP-Final Inspection12/14/200712/17/200712/17/2007 12:55:49 PMAPASS
Verified as-built plans, noted one minor change, permit finaled.
FIR07-00036 INSP-Final Inspection12/14/200712/17/200712/17/2007 12:53:05 PMAPASS
Final inspection passed, noted one head as shown on plans in a water closet is not installed due to ft2 less than 55.
FIR07-00029 INSP-Final Inspection12/14/200712/17/200712/17/2007 12:50:30 PMANR
No plans provided for inspection, construction is underway, project is not in condition for final approval at this time.
BLD07-01562 FIRE-Final Inspection12/14/200712/17/200712/17/2007 12:47:36 PMAPASS
Items on correction notice are complete, fire life safety finaled.
FIR07-00884 INSP-Sprinkler Rough-in12/14/200712/17/200712/14/2007 2:29:25 PMACANC
Need a partial cover, Brian D is the contact. Thank you. Phone #: ###-#### Internet Inspection Request from: Stan Beus Inspection cancelled from web by: Stan Beus
FIR07-00877 INSP-Final Inspection12/14/200712/17/200712/14/2007 2:28:44 PMACANC
Brian D is the contact, thank you. Phone #: ###-#### Internet Inspection Request from: Stan Beus Inspection cancelled from web by: Stan Beus