ELE08-00528
| ELE-Aging Inspection | 12/17/2008 | 12/17/2008 | 12/18/2008 9:46:32 AM | | CANC |
|
|
|
ELE08-00529
| ELE-Aging Inspection | 12/17/2008 | 12/17/2008 | 12/18/2008 9:45:33 AM | | CANC |
|
|
|
ELE08-01749
| Final | 12/17/2008 | 12/17/2008 | 12/17/2008 3:33:48 PM | P | PASS |
|
|
Eric Phone #: ###-#### ok called outllet covered in upstairs fam rm called Eric will uncover and install recept
|
ESC08-00800
| General Inspection | 12/17/2008 | 12/17/2008 | 12/17/2008 3:31:16 PM | P | PASS |
|
|
|
ELE08-02947
| Final | 12/17/2008 | 12/17/2008 | 12/17/2008 3:30:40 PM | P | PASS |
|
|
calvin Phone #: ###-#### ok corr. made
|
ELE08-03200
| Electrical Rough-In | 12/17/2008 | 12/17/2008 | 12/17/2008 2:34:10 PM | P | PART |
|
|
darren Phone #: ###-#### ok MC repaired
|
ELE08-03246
| Electrical Rough-In | 12/17/2008 | 12/17/2008 | 12/17/2008 1:43:03 PM | P | PART |
|
|
Please call to meet Phone #: ###-#### Internet Inspection Request from: mark morris walls in conference rm and education class rm in basement
|
ELE08-02833
| Final | 12/17/2008 | 12/17/2008 | 12/17/2008 1:41:48 PM | P | CANC |
|
|
john - late afternoon please Phone #: ###-#### contr called and canceled
|
ESC08-00990
| General Inspection | 12/17/2008 | 12/17/2008 | 12/17/2008 12:27:10 PM | P | PASS |
|
|
ok
|
ELE08-03216
| Permanent Service | 12/17/2008 | 12/17/2008 | 12/17/2008 12:26:05 PM | P | PASS |
|
|
glen Phone #: ###-#### p/s u/g new ok
|
ELE08-02642
| Final | 12/17/2008 | 12/17/2008 | 12/17/2008 12:25:41 PM | P | FAIL |
|
|
george Phone #: ###-#### need documentation of area 500.4(A) posted, 210.5(C) ID and permanent labels for branch circuits of 480 V, and 120/208 V, 250.32 GEC foe old xformer, B M C 4-05-33 label and listing for field evaluated equipment that was moved from original location called
|
ELE08-02905
| Electrical Rough-In | 12/16/2008 | 12/17/2008 | 12/17/2008 10:54:58 AM | A | PART |
|
|
Please provide partial rough-in inspection. Phone #: ###-#### Internet Inspection Request from: Spencer Mclean walls and soffits anop
|
ELE08-03065
| Electrical Rough-In | 12/16/2008 | 12/17/2008 | 12/17/2008 10:54:30 AM | A | PART |
|
|
daniel Phone #: ###-#### walls office and restrms
|
ELE08-02756
| Electrical Rough-In | 12/16/2008 | 12/17/2008 | 12/17/2008 9:48:01 AM | A | FAIL |
|
|
brian - please call 1/2 hr prior Phone #: ###-#### met owner, equip grd cut to short, needs 6" free length, splices are loose
|
ELE08-02832
| Final | 12/16/2008 | 12/17/2008 | 12/17/2008 9:28:31 AM | A | PASS |
|
|
Ready for final on repair and rewire from house fire thanks Phone #: ###-#### Internet Inspection Request from: Lynn Cable ok
|
ELE08-02665
| Final | 12/16/2008 | 12/17/2008 | 12/17/2008 8:54:52 AM | A | FAIL |
|
|
lee - Phone #: no ready called fee due
|
ELE08-03088
| Final | 12/16/2008 | 12/17/2008 | 12/17/2008 8:28:54 AM | A | CANC |
|
|
ceiling final Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot see added r/i
|
ELE08-03088
| Electrical Rough-In | 12/17/2008 | 12/17/2008 | 12/17/2008 8:28:37 AM | A | PART |
|
|
ceiling final Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot NO FINAL CEILING R/I OK
|