Inspections for the day of: Wednesday, December 17, 2008.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00628 INSP-Sprinkler Rough-in12/17/200812/17/200812/17/2008 4:37:35 PMPPASS
See the city approved plans for the location on the second floor where the sprinkler piping is ok to cover.
FIR08-00341 INSP-Alarm Testing12/16/200812/17/200812/17/2008 4:26:50 PMADONE
Additional initiating devices were tested today. See the city approved plans for devices. The fire alarm plans need to be resubmitted showing the door magnets. Also the fire alarm panel is having undefined troubles showing up and the graphic annunciator is not operating. No more testing will be done until the fire alarm system is completely functional.
FIR08-00584 INSP-Final Inspection12/16/200812/17/200812/17/2008 3:08:37 PMAFAIL
Provide map at the facp, provide smoke detector over the panel and provide as-builts.
FIR08-00647 INSP-Final Inspection12/16/200812/17/200812/17/2008 3:07:58 PMAPASS
Permit finaled
BLD08-02156 FIRE-Final Inspection12/16/200812/17/200812/17/2008 9:20:44 AMAPASS
Life safety passed