BLD09-01623
| FIRE-Final Inspection | 12/17/2009 | 12/17/2009 | 12/17/2009 4:12:29 PM | P | PASS |
|
|
Life safety completed acceptable, inspection passed.
|
BLD09-01909
| FIRE-Final Inspection | 12/17/2009 | 12/17/2009 | 12/17/2009 4:10:56 PM | P | PASS |
|
|
Corrections completed, fire life safety passed.
|
FIR09-00696
| INSP-Final Inspection | 12/17/2009 | 12/17/2009 | 12/17/2009 4:10:20 PM | P | PASS |
|
|
Fire sprinkler permit finaled.
|
FIR09-00696
| INSP-Final Inspection | 12/16/2009 | 12/17/2009 | 12/17/2009 2:55:05 PM | A | PASS |
|
|
Scope of fire sprinker work completed satisfactory, inspection passed.
|
BLD09-02061
| FIRE-Final Inspection | 12/16/2009 | 12/17/2009 | 12/17/2009 2:53:29 PM | A | FAIL |
|
|
Door hardware is not approved at the common exit from the three new offices, the existing fire sprinkler system is overdue annual certification.
|
FIR09-00702
| INSP-Sprinkler Rough-in | 12/16/2009 | 12/17/2009 | 12/17/2009 2:51:38 PM | A | FAIL |
|
|
Overhead modifications need to be exposed for inspection.
|
FIR09-00364
| INSP-Sprinkler Rough-in/Hydro | 12/16/2009 | 12/17/2009 | 12/17/2009 2:50:18 PM | A | FAIL |
|
|
Overhead hydrostatic testing failed due to pressure loss at the guage and visible leakage at two locations.
|
BLD09-01918
| FIRE-Final Inspection | 12/16/2009 | 12/17/2009 | 12/17/2009 9:58:13 AM | A | PASS |
|
|
Correction items are finished, life safety finaled.
|
FIR09-00364
| INSP-Sprinkler Rough-in/Hydro | 12/14/2009 | 12/17/2009 | 12/16/2009 3:48:02 PM | A | CANC |
|
|
Final - Contact: Todd Phone #: ###-#### x1234 Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley
|